24
To determine the combustion efficiency
one must make the following measurements:
- measurement of the combustion air temperature
taken in the relevant hole
2
.
1
1
1
A
B
C
COAXIAL PIPEs
sEPARATE PIPEs
PIPEs Ø 80 TYPE B23
Flue gas
probe
Air
probe
Air
probe
Flue
gas
probe
Air
probe
Air
probe
2
2
2
3.11 - MEAsUREMENT OF COMBUsTION EFFICIENCY DURING INsTALLATION
- measurement of the flue gas temperature and
content of CO
2
taken in the relevant hole
1
.
Take the measurements with the generator in
steady state conditions (see par. 3.11.1).
ATTENTION!
Function reserved for Authorised
Assistance Centres only.
3.11.1- ACTIvATION OF THE CALIBRATION FUNCTION
3.11.2 - POsITIONING THE PROBEs
1
ACTIvATION
By pressing the button (
D
) for 3 seconds, the
calibration function is activated. Release it when
the SERVICE symbol appears,
Do not press it for
more than 9’’ (par. 4.2)
This function is not activat-
ed if there is a block or domestic hot water request.
2
MAXIMUM OUTPUT
By turning the knob (B) onto MAX, the boiler will
operate at
maximum output:
- 3 illuminated symbols
4
DIsABLING
The “calibration” function stays active for 15 min
-
utes.
To disable the
CALIBRATION
function before the
time elapses, switch the boiler on and off again by
acting on the main switch
.
3
MINIMUM OUTPUT
By turning the knob (B) in position , the boiler
will operate at
minimum output
:
- 2 illuminated symbols
- 1 flashing
The user is NOT authorised to activate
the function described below.
Summary of Contents for KON C 18
Page 2: ...2 http www unicalag it prodotti domestico 50 condensazione gas 774 kon ...
Page 10: ...10 KON R 28 R 35 KON C 28 C 35 Vista dall alto KON C 28 C 35 Vista da sotto ...
Page 36: ...2 http www unicalag it prodotti domestico 50 condensazione gas 774 kon ...
Page 44: ...10 KON R 28 R 35 KON C 28 C 35 View from above KON C 28 C 35 View from below ...
Page 70: ......
Page 71: ......