38
Instructions for the installer
-
Check that the boiler is connected to the electrical
supply; the green indicator led “Q” (
) on the control
panel must be illuminated.
-
Create a request in CH by pressing key indicate.
-
Turn the gas valve knob, in OFF position.
-
After 1sec, boiler switch off,
LIGHT
BLUE
-
Power on by switching ON-OFF switch
3.27 -
TESTING THE IGNITION SAFETY
SHUT OFF DEVICE
Lock-out indicator
led illuminated
+ fault indicator led
-
Press Reset Key will displayed the fault code LF (loss
of flame), the boiler will retry ignition cycle (7 seconds)
after which if was not removed the cause of the fault
(gas tap) the boiler will shut off.