27
Installation instructions
LIST OF PARAMETERS
Parameter
Boiler operating temperature (°C)
0
Minimum boiler temperature (°C)
1
Maximum boiler temperature for alarm (°C)
2
Start temperature for filling storage tank (°C).
3
End temperature for filling storage tank (°C).
4
Maximum temperature for storage tank (solar protection) (°C).
5
Thermostat control temperature tolerance band for heating (°C)
6
Temperature tolerance band for filling storage tank (°C)
7
Maximum temperature tolerance band for boiler body (°C)
8
Temperature tolerance band for operating solar panels (°C)
9
PROBE CONFIGURATION PARAMETER
28
Parameter to be used for configuring probes
FUNCTIONAL CONFIGURATION PARAMETER
29
Parameter to be entered for functional settings
Language selection: 0 = Italian - 2 = English - 4 = French - 6 = Spanish
30
DEFAULT
SETTINGS
Maximum operating time of burner (hours)
10
Number of burner start-up attempts
11
Duration of burner flame ignition cycle (minutes)
12
Time for detecting stability of burner flame (seconds)
13
Modulation of fuel and air in relation to boiler temperature
14
Time for cleaning burner (seconds)
15
Time for post-rotation of feeding screw 2 (seconds)
21
Time for pre-igniting the burner (seconds)
16
Time for preloading fuel (seconds)
17
Pre-combustion/combustion time (minutes)
18
Time for running the feeding screw motor ON (seconds)
19
Time for pausing the feeding screw motor OFF (seconds)
20
Time for final cleaning of burners (seconds)
22
Fan speed with burner running
23
Fan speed during burner combustion
24
Maximum operating temperature of the solar panels (°C)
25
Minimum flue gas temperature for detecting start-up of burner (°C)
26
Maximum gas flue temperature of burner with modulation of -15°C
27
75
60
90
55
65
90
5
6
4
10
0
0
0
8
16
24
0
0
0
0
0
0
5
2
15
30
6
40
5
60
55
5
14
11
5
170
230
160
60
245
Probe 0 at 0 if absent or at -1 if present
Probe 2 at 0 if absent or at -2 if present
Probe 3 at 0 if absent or at -4 if present
Probe 4 at 0 if absent or at -8 if present
Probe 5 at 0 if absent or at -16 if present
Def. 1 = at 0 if storage tank absent or at -1 if storage tank present
Def. 2 = at 0 if coil-type storage tank or at -2 if Combi or Puffer storage tank
Def. 3 = at 0 if solar panel absent or at -4 if solar panel present
Def. 4 = at 0 for optical ignition detection or at -8 for flue gas ignition detection
Summary of Contents for PELLEXIA 80