21
Instructions for the installer
Perdita di carico lato acqua
0
0,5
1
1,5
2
2,5
3
0
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000 11000 12000 13000 14000 15000 16000 17000 18000 19000 20000
21000 22000 23000 24000
Q : portata acqua (l/h)
p
e
rd
it
a d
i car
ic
o
(
m
m
h
2O
)
PK150X 2S
230 300 348
8994
11781 13660
11992
15708 18213
150
5870
7826
Power supply in kW
Max flow rate
demanded in l/h ( t=15 K)
Δ
Nominal flow rate
requested in l/h ( t=20 K)
Δ
3.12 - DETERMINATION OF PRIMARY CIRCUIT PUMP OR BOILER SYSTEM PUMP
The boiler pump must have a delivery head which can
ensure the water flow rate as shown in the graph "Water
pressure losses".
The following table gives an indication of the pump's flow
rate in function of the ?t of the primary circuit.
The size of the pumps must be determined
by installers or technical engineers accor-
ding to boiler data and system design.
The water side resistance curve of the boiler
is shown in the following graph.
The pump is not an integral part of the boiler.
We recommend you choose a pump with the
rate and discharge head at about 2/3 of its
characteristic curve.
Q:
water flow rate
(l/h)
WATER SIDE PRESSURE LOSSES
Pressure losses
(mmH2O)