30
SPK 230 - SPK 300 - SPK 400 - SPK 500 - SPK 600
1) Maximum output adjustment
- operate the boiler in “calibration” mode at mAXImum out-
Put (see 3.11.1)
- once the burner is on check
that the “mAXImum” co2 output value corresponds to that
indicated in the table “NOZZLES - PRESSURE”.
- if it does not correspond, correct it by turning screw
“S”
cLocKWISE to increase it, ANtIcLocKWISE to decrease
it.
(see table NOZZLES-CAPACITY-PRESSURE)
.
2) Minimum output adjustment
- operate the boiler in “calibration” mode at mINImum outPut
(see 3.11.1)
- once the burner is on, check that the “mINImum” co2 output
value corresponds to what is indicated in the table “NOZZLES
- PRESSuRE”.
- If necessary, adjust the value by turning (with a 2.5 mm hex
key) screw
“R”
cLocKWISE to increase it, ANtIcLocK-
WISE to decrease it
(see table NOZZLES-CAPACITY-PRESSURE)
.
(S) MAXIMUM OUTPUT ADJUSTMENT SCREW
(R) MINIMUM OUTPUT ADJUSTMENT SCREW
GAS VALVE (Side view)
PG = GAS PRESSURE SWITCH
(*) ONLY ON SPK 400 / 500 / 600