32
NOZZLES - PRESSURE - FLOW RATES TABLE
SPK 230
Type of Gas
Supply Press.
Ø Noz-
zlesi
Opening
VG Shutter
Fan speed
CO
2
levels
Furnace
power
[mbar]
(mm)
[mm]
min
max
[%]
[%]
FL
[% FU]
FH
[% FU]
min
max
IG
Nat. gas (G20)
20
15
6,0
32
86
9,2
9,2
35
Propane (G31)
37
15
2,5
32
82
10,5
10,5
35
SPK 300
Type of Gas
Supply Press.
Ø Noz-
zlesi
Opening
VG Shutter
Fan speed
CO
2
levels
Furnace
power
[mbar]
(mm)
[mm]
min
max
[%]
[%]
FL
[% FU]
FH
[% FU]
min
max
IG
Nat. gas (G20)
20
15
9,0
32
83
9,2
9,2
45
Propane (G31)
37
15
3,0
32
81
10,5
10,5
45
SPK 400
Type of Gas
Supply Press.
Ø Noz-
zlesi
Opening
VG Shutter
Fan speed
CO
2
levels
Furnace
power
[mbar]
(mm)
[mm]
min
max
[%]
[%]
FL
[% FU]
FH
[% FU]
min
max
IG
Nat. gas (G20)
20
18
12,3
32
76
9,1
9,1
45
Propane (G31)
37
18
6,0
36
69
10,8
10,8
45
SPK 500
Type of Gas
Supply Press.
Ø Noz-
zlesi
Opening
VG Shutter
Fan speed
CO
2
levels
Furnace
power
[mbar]
(mm)
[mm]
min
max
[%]
[%]
FL
[% FU]
FH
[% FU]
min
max
IG
Nat. gas (G20)
20
18
18,3
32
88
9,2
9,2
35
Propane (G31)
37
18
6,3
33
83
10,8
10,8
35
SPK 150
Type of Gas
Supply Press.
Ø Noz-
zlesi
Opening
VG Shutter
Fan speed
CO
2
levels
Furnace
power
[mbar]
(mm)
[mm]
min
max
[%]
[%]
FL
[% FU]
FH
[% FU]
min
max
IG
Nat. gas (G20)
20
9
NO
31
99
9,3
9,3
50
Propane (G31)
37
9
NO
31
94
10,5
10,5
50
SPK 600
Type of Gas
Supply Press.
Ø Noz-
zlesi
Opening
VG Shutter
Fan speed
CO
2
levels
Furnace
power
[mbar]
(mm)
[mm]
min
max
[%]
[%]
FL
[% FU]
FH
[% FU]
min
max
IG
Nat. gas (G20)
20
20
21
29
88
9,1
9,1
35
Propane (G31)
37
18
6,3
30
92
10,7
10,7
35