28
Description
Value range
Default
Individual values
SEQuENCE mOdE
01 - 06
1
SEQuENCE CHANGE
10 - 800 HOurS
200 HOurS
CYCLE BLOCK
00 min - 30 min
00 min
HYSTErESIS BurNEr 2
2K - 20K
2K
BOILEr COOLING FuNCTION
00 - 01
0
BOILEr COOLING TEmPErATurE
30°C - 120°C
95
HS 1 TYPE
00 - 06
6
HS 1 BuS
00 - 04
4
HS 2 TYPE
00 - 05
0
HS 2 STOrAGE TANK
01 - 03
0
PuFFEr TYPE
01 - 01 - 02
0
SCrEEd
00, 01 (OFF - ON)
00 OFF
SCrEEd PrOGrAm
** see note
(*)
set value of first stage of first boiler at 1, in the second leave dashes
all other boiler stages must be disabled.
(**)
see e8.5064 heating controller instruction book
dOMesTic hOT waTer prOdUcTiOn
Description
Value range
Default
Individual values
CHArGE PumP
00 - 01 (OFF / ON)
01 (ON)
PArALLEL PumP ruNNING
00 , 01, 02, 03
1
T dHW
00K - 50K
20K
dHW HYSTErESIS
5K - 30K
5 dEGrEES
dHW FOLLOWuP
00 mIN - 30 mIN
00 mIN
THErmOSTAT INPuT
00, 01 (OFF / ON)
00 OFF
THErmOSTAT FuNCTIONING
00, 01 (OFF / ON)
00 OFF
LOAd THrOuGH
00, 01 (OFF / ON)
00 OFF
rETurN
exit level using
heaTing circUiT 1
Description
Value range
Default
Individual values
HEATING CIrCuIT FuNCTION
00 - 04
0
PumP mOdE
00 - 03
0
mIXEr OPEN
----
mIXEr CLOSEd
----
mAX FLOW TEmPErATurE
20 °C - 110 °C
80 °C
mIN FLOW TEmPErATurE
10 °C - 110 °C
30 °C
FrOST PrOTECTION TEmP
(-15)°C - (5)°C
0 °C
OuTSIdE TEmP dELAY
0:00 - 24:00
0,00
HEATING SLOPE dISTANCE
00K - 50K
5 °C
B-HEAT SINK
00 - 01 (OFF / ON)
1
rETurN