background image

12 

OM-FX SERIES

Service

This piece of equipment uses a R290 Refrigeration system.  This equipment has been 

clearly marked on the serial tag the type of refrigerant that is being used.   There is also a 

warning labels stating that the unit contains R290 refrigerant. 

No smoking or open flames when servicing this equipment.  If needed, use a CO

2

 or 

dry=power type fire extinguisher

Only authorized service technician, certified in R290 system should service this equipment.

MANIFOLD SET

A R134A manifold set can be used for servicing this equipment.  

REFRIGERANT RECOVERY

Follow all national and local regulations for R-290 refrigerant recovery.  

LEAKING CHECKING AND REPAIR

Leak check an R-290 system the same way you would an R-134a or R-404A system with 

the following exceptions. 

1.  Do not use a Halid leak detector on a R290 system.

2.  Electronic leak detector must be designated specifically for combustible gas.

Use of a bubble solution or an ultrasonic leak detector are acceptable.   

When repairing a leak, it is recommended using oxygen free dry nitrogen with a trace gas 

not exceeding 200PSI. 

When accessing an R290 system, piercing valves are not to remain on the equipment in 

a permanent manner. After charge is recovered, Schrader valves are to be installed on the 

process stubs.  Proper charge is to be weighed into the system and the system is to be 

leak checked afterwards.

The R290 equipment must have red process tubes and other devices through which the 

refrigerant is serviced, such as any service port.  This color marking must remain on the 

equipment.  If marking is removed, it must be replace and extend at least 2.5 centimeters 

(1”) from the compressor.

CHARGING

Follow the charge amount specified on the data tag.  It is recommended to use the shortest 

hoses possible to prevent undercharging.

•  Ensure the system is sealed and leak checked 

•  Evacuate system to a minimum 500 micron

•  Weigh in correct charge

•  Leak check the system again

•  Bleed the refrigerant from the high side hose to the low side hose

•  Disconnect the hoses

•  Remove line taps

CAUTION!

COMPONENT PARTS SHALL BE REPLACED 

WITH LIKE COMPONENTS. SERVICE WORK 

SHALL BE DONE BY FACTORY AUTHORIZED 

SERVICE PERSONNEL, SO AS TO MINIMIZE 

THE RISK OF POSSIBLE IGNITION DUE TO 

INCORRECT PARTS OR IMPROPER SERVICE.

Summary of Contents for Randell FX Series

Page 1: ...ammable vapors and liquids in the vicinity of this or any other appliance WARNING R290 flammable refrigerant in use Improper installation adjustment alteration service or maintenance can cause propert...

Page 2: ...g page 4 5 Equipment Description page 6 Installation page 7 Operation page 8 9 Maintenance page 10 Troubleshooting page 11 Service page 12 Parts List page 13 16 Electrical Schematic page 17 Service Lo...

Page 3: ...roper maintenance will provide years of trouble free service to its owner In addition all Unified Brands food service equipment is backed by some of the best warranties in the food service industry an...

Page 4: ...4 OM FX SERIES The following warning labels will be found on your equipment INTERIOR EVAPORATOR COVER NEAR MACHINE COMPARTMENT AND NAMEPLATE Labeling...

Page 5: ...OM FX SERIES 5 EXTERIOR OF UNIT NEAR EXPOSED REFRIGERANT TUBING Labeling...

Page 6: ...0 1 3 4 5 15P 2 635 FX 2WSA 290 43 3 28 36 2 2 5 1 58 3 4 1 4 2 115 60 1 3 4 5 15P 2 635 FX 2WSRE 290 35 34 5 36 2 2 6 2 1 76 3 3 1 4 2 115 60 1 3 4 5 15P 2 635 FX 2WSREA 290 35 34 5 33 2 5 1 58 3 4 1...

Page 7: ...adjustments are required the control is located on the front panel Confirm that the unit is holding the desired temperature 5 Refer to the front of this manual for serial number location Please recor...

Page 8: ...ol adjustment until desired temperature is reached DANFOSS CONTROLLER OPERATION LED FUNCTION Compressor energized Evaporator fan de energized Defrost in progress Fans delay after defrost completion Ev...

Page 9: ...ng Alarms Visual Display Only 1 After 2 minutes the display will flash the alarm message dor 2 Press any button to acknowledge alarm DRAWER DOOR ALARM Door Alarm Activation If audible alarm is wanted...

Page 10: ...t is the ultimate necessity in preventing costly repairs By evaluating each unit on a regular schedule you can often catch and repair minor problems before they completely disable the unit and become...

Page 11: ...ll for service at 888 994 7636 Unit too cold Incorrect set point Adjust control set point Unit too warm Door drawer ajar Ensure door drawer is fully closed Gasket torn or out of place Inspect the gask...

Page 12: ...n free dry nitrogen with a trace gas not exceeding 200PSI When accessing an R290 system piercing valves are not to remain on the equipment in a permanent manner After charge is recovered Schrader valv...

Page 13: ...PHILLIPS TRUSS SS 3 FA NUT0312 RIVNUT 6 32 THD 4 RF CMP1604 COMPRESSOR 3 8 HP LO 404 115V DANFOSS 4a RF CMP1604SC COMPRESSOR START COMPONENTS 5 RF FLT9902 DRYER 1 4x 042 FILTER EKP 032 SC DBL INL CAP...

Page 14: ...SIDE EXTERIOR S S LEFT 6 RP BCK1701 BACK EXTERIOR 7 HD TRK1101_BASE TRACK DWR SLIDE L H 2 1 8 X 28 BAYONET MNT 8 HD TRK1102_BASE TRACK DWR SLIDE R H 2 1 8 X 26 650MM BAYONET MNT 9 RP CPN0601 PAN COND...

Page 15: ...EA 1B RP PAN0801 INSULATED DRAWER TUB FOR FX 1UC 2 RP GSK0604 GASKET MAGNETIC SLIDE SEAL PF 765 X 614mm 3 RP DWR1603 DRAWER CARRAIGE ASSY W FRONT FX 1 FX 1RE 3A RP DWR1504 DRAWER CARRIAGE ASSY W FRONT...

Page 16: ...MIT 6 RF TRM0501 THERMODISC 2 WIRE OPEN 70 CLOSE 50 SEO 70 T17 7 RP GSK0604 GASKET MAGNETIC SLIDE SEAL PF 765 X 614mm 8 RF DIF0601 DIFFUSER LID FOR FX 1 FX 1A FX 1RE FX 1REA 8A RF DIF0801 DIFFUSER LID...

Page 17: ...OM FX SERIES 17 Electrical Schematic...

Page 18: ...18 OM FX SERIES Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By...

Page 19: ...f the customer LABOR COVERAGE In the unlikely event a Unified Brands manufactured unit fails due to defects in materials or workmanship within the first ninety days Unified Brands agrees to pay the co...

Page 20: ...er cleaning temperature adjustments clogged drains unit leveling and re application of silicone 2 Unified Brands does not cover gaskets under warranty Gaskets are a maintenance type component that are...

Page 21: ...o minimize liability a full inspection is necessary upon arrival Appearance of damage will require removing the crate in the presence of the driver A notation must be placed on the freight bill and si...

Reviews: