background image

OM-FX SERIES       7

Installation

SELECTING A LOCATION FOR YOUR NEW UNIT

The following conditions should be considered when selecting a location for your unit:

1. 

Floor and Countertop Load: 

 The area on which the unit will rest must be level, free 

of vibration, and suitably strong enough to support the combined weights of the unit 

plus the maximum product load weight. 

2. 

Clearance

:  Clearance must be a combined total of at least 1” on back of unit for FX-

1RE(A)-290. Do not place any object that can block the ventilation exhaust from the 

machine compartment register. Area of equipment must be free of all combustible 

materials.

3. 

Ventilation

:  The air cooled self contained unit requires a sufficient amount of cool 

clean air.  Avoid surrounding your FX unit around other heat generating equipment 

and out of direct sunlight.  Also, avoid locating in an unheated room or where the 

room temperature may drop below 70° F or rise above 100° F.

INSTALLATION CHECKLIST

After the final location has been determined, refer to the following checklist prior to 

start-up:

1.  Check all exposed refrigeration lines to ensure that they are not kinked, dented, or 

rubbing together.

2.  Check that the condenser and evaporator fans rotate freely without striking any 

stationary members.

3.  Unit must be properly leveled; check all legs or casters to ensure they all are in 

contact with the floor while maintaining a level work surface.  Adjusting bullet 

feet heights or shimming casters may be necessary if the floor is not level.  NOTE:  

Damage to equipment may result if not followed.  Unified Brands is not responsible 

for damage to equipment if improperly installed.

4.  Allow unit time to cool down to temperature. If temperature adjustments are required, 

the control is located on the front panel.  Confirm that the unit is holding the desired 

temperature.  

5.  Refer to the front of this manual for serial number location. Please record this 

information in your manual on page 3 now. It will be necessary when ordering 

replacement parts or requesting warranty service.

6.  Before putting in food, allow your unit to operate for approximately two (2) hours so 

that interior of the unit is cooled down to storage temperature.

7.  Check drawer to ensure the drawer slides freely and fully extends along with seating 

into the cabinet properly when closed.

ELECTRICAL SUPPLY

Any wiring should be done by a qualified electrician in accordance with all national and 

local electrical codes.  A properly wired and grounded outlet will assure proper operation.  

Please consult the data tag attached to the compressor to ascertain the correct electrical 

requirements.  Supply voltage and amperage requirements are located on the serial 

number tag (see page 3 for location). 

CAUTION!

THIS UNIT CONTAINS R290 FLAMMABLE 

REFRIGERANT.  USE CAUTION WHEN 

HANDLING MOVING AND USE OF THE 

REFRIGERATOR OR FREEZER.  AVOID 

DAMAGING THE REFRIGERANT TUBING OR 

INCREASE THE RISK OF A LEAK. 

FAILURE TO FOLLOW INSTALLATION 
GUIDELINES AND RECOMMENDATIONS MAY 
VOID THE WARRANTY ON YOUR UNIT.

IT IS IMPORTANT THAT YOUR UNIT HAS 
ITS OWN DEDICATED LINE.  CONDENSING 
UNITS ARE DESIGNED TO OPERATE WITH 
A VOLTAGE FLUCTUATION OF PLUS OR 
MINUS 10% OF THE VOLTAGE INDICATED 
ON THE UNIT DATA TAG.  BURN OUT OF A 
CONDENSING UNIT DUE TO EXCEEDING 
VOLTAGE LIMITS WILL VOID THE WARRANTY.

THE DANFOSS CONTROLLER HAS LOW 
VOLTAGE PROTECTION AND WILL NOT 
OUTPUT VOLTAGE TO THE COMPRESSOR IF 
VOLTAGE IS LESS THAN 104V.

THIS UNIT IS INTENDED FOR USE IN 
LABORATORIES IN COMMERCIAL, 
INDUSTRIAL, OR INSTITUTIONAL 
OCCUPANCIES AS DEFINED IN THE SAFETY 
STANDARD FOR REFRIGERATION SYSTEMS, 
ASHRAE 15. 

Summary of Contents for Randell FX Series

Page 1: ...ammable vapors and liquids in the vicinity of this or any other appliance WARNING R290 flammable refrigerant in use Improper installation adjustment alteration service or maintenance can cause propert...

Page 2: ...g page 4 5 Equipment Description page 6 Installation page 7 Operation page 8 9 Maintenance page 10 Troubleshooting page 11 Service page 12 Parts List page 13 16 Electrical Schematic page 17 Service Lo...

Page 3: ...roper maintenance will provide years of trouble free service to its owner In addition all Unified Brands food service equipment is backed by some of the best warranties in the food service industry an...

Page 4: ...4 OM FX SERIES The following warning labels will be found on your equipment INTERIOR EVAPORATOR COVER NEAR MACHINE COMPARTMENT AND NAMEPLATE Labeling...

Page 5: ...OM FX SERIES 5 EXTERIOR OF UNIT NEAR EXPOSED REFRIGERANT TUBING Labeling...

Page 6: ...0 1 3 4 5 15P 2 635 FX 2WSA 290 43 3 28 36 2 2 5 1 58 3 4 1 4 2 115 60 1 3 4 5 15P 2 635 FX 2WSRE 290 35 34 5 36 2 2 6 2 1 76 3 3 1 4 2 115 60 1 3 4 5 15P 2 635 FX 2WSREA 290 35 34 5 33 2 5 1 58 3 4 1...

Page 7: ...adjustments are required the control is located on the front panel Confirm that the unit is holding the desired temperature 5 Refer to the front of this manual for serial number location Please recor...

Page 8: ...ol adjustment until desired temperature is reached DANFOSS CONTROLLER OPERATION LED FUNCTION Compressor energized Evaporator fan de energized Defrost in progress Fans delay after defrost completion Ev...

Page 9: ...ng Alarms Visual Display Only 1 After 2 minutes the display will flash the alarm message dor 2 Press any button to acknowledge alarm DRAWER DOOR ALARM Door Alarm Activation If audible alarm is wanted...

Page 10: ...t is the ultimate necessity in preventing costly repairs By evaluating each unit on a regular schedule you can often catch and repair minor problems before they completely disable the unit and become...

Page 11: ...ll for service at 888 994 7636 Unit too cold Incorrect set point Adjust control set point Unit too warm Door drawer ajar Ensure door drawer is fully closed Gasket torn or out of place Inspect the gask...

Page 12: ...n free dry nitrogen with a trace gas not exceeding 200PSI When accessing an R290 system piercing valves are not to remain on the equipment in a permanent manner After charge is recovered Schrader valv...

Page 13: ...PHILLIPS TRUSS SS 3 FA NUT0312 RIVNUT 6 32 THD 4 RF CMP1604 COMPRESSOR 3 8 HP LO 404 115V DANFOSS 4a RF CMP1604SC COMPRESSOR START COMPONENTS 5 RF FLT9902 DRYER 1 4x 042 FILTER EKP 032 SC DBL INL CAP...

Page 14: ...SIDE EXTERIOR S S LEFT 6 RP BCK1701 BACK EXTERIOR 7 HD TRK1101_BASE TRACK DWR SLIDE L H 2 1 8 X 28 BAYONET MNT 8 HD TRK1102_BASE TRACK DWR SLIDE R H 2 1 8 X 26 650MM BAYONET MNT 9 RP CPN0601 PAN COND...

Page 15: ...EA 1B RP PAN0801 INSULATED DRAWER TUB FOR FX 1UC 2 RP GSK0604 GASKET MAGNETIC SLIDE SEAL PF 765 X 614mm 3 RP DWR1603 DRAWER CARRAIGE ASSY W FRONT FX 1 FX 1RE 3A RP DWR1504 DRAWER CARRIAGE ASSY W FRONT...

Page 16: ...MIT 6 RF TRM0501 THERMODISC 2 WIRE OPEN 70 CLOSE 50 SEO 70 T17 7 RP GSK0604 GASKET MAGNETIC SLIDE SEAL PF 765 X 614mm 8 RF DIF0601 DIFFUSER LID FOR FX 1 FX 1A FX 1RE FX 1REA 8A RF DIF0801 DIFFUSER LID...

Page 17: ...OM FX SERIES 17 Electrical Schematic...

Page 18: ...18 OM FX SERIES Service Log Model No Purchased From Serial No Location Date Purchased Date Installed Purchase Order No For Service Call Date Maintenance Performed Performed By...

Page 19: ...f the customer LABOR COVERAGE In the unlikely event a Unified Brands manufactured unit fails due to defects in materials or workmanship within the first ninety days Unified Brands agrees to pay the co...

Page 20: ...er cleaning temperature adjustments clogged drains unit leveling and re application of silicone 2 Unified Brands does not cover gaskets under warranty Gaskets are a maintenance type component that are...

Page 21: ...o minimize liability a full inspection is necessary upon arrival Appearance of damage will require removing the crate in the presence of the driver A notation must be placed on the freight bill and si...

Reviews: