34
ELECTRICAL CURRENT
(Free cooling version)
COMPRESSOR
circuit 1
COMPRESSOR
circuit 2
FANS
MODEL
VOLTAGE
No. kW
OA
FLA LRA No. kW
OA
FLA LRA No. kW
OA
FLA
00152
400V/3ph
50Hz
1
5.9
11.4
15
98
1
5.9
11.4
15
98
4
0.30 1.37
1.8
00182
400V/3ph
50Hz
1
5.9
11.4
15
98
1
8.8
16
21
130
4
0.30 1.37
1.8
00202
400V/3ph
50Hz
1
8.8
16
21
130
1
8.8
16
21
130
4
0.30 1.37
1.8
00232
400V/3ph
50Hz
1
8.8
16
21
130
1
11
21
26
175
6
0.30 1.37
1.8
00252
400V/3ph
50Hz
1
11
21
26
175
1
11
21
26
175
6
0.30 1.37
1.8
00302
400V/3ph
50Hz
1
13.5
24
30
175
1
13.5
24
30
175
6
0.30 1.37
1.8
KW :
(kW)
Power absorbed in nominal conditions (water 12/7°C; outdoor 35 °C) (
1
)
OA :
(A)
Nominal operating current (
1
)
FLA :
(A)
Full load current (
1
)
LRA :
(A)
Start-up (
1
)
(
1
) :
per motor
PUMPS (optionals)
Free cooling
PUMP
COMPLETE UNIT
base version
MODEL
VOLTAGE
N
(
1
)
TYPE kW
OA
FLA LRA
KW
OA
kW
OA
FLA
LRA
00152
400V/3ph
50Hz
1
A
1.34
2.4
-
10.8
0.81
1.5
13.8
29.8
38.7
123.7
00182
400V/3ph
50Hz
1
A
1.34
2.4
-
10.8
0.81
1.5
16.7
34.4
44.7
155.7
00202
400V/3ph
50Hz
1
A
1.34
2.4
-
10.8
0.81
1.5
19.6
39.0
50.7
167.7
00232
400V/3ph
50Hz
1
B
1.5
2.8
-
16.8
0.81
1.5
22.4
46.7
59.3
216.3
00252
400V/3ph
50Hz
1
B
1.5
2.8
-
16.8
0.81
1.5
24.6
48.2
64.3
222.3
00302
400V/3ph
50Hz
1
B
1.5
2.8
-
16.8
0.81
1.5
27.6
56.0
72.3
222.3
(
1
) N :
indicates the number of pumps functioning simultaneously; even in units with two pumps, one is always in stand-by.