Close Control Regulation Program
06MC0071@00B0110
01/10/2012
37
This screen is used to set:
Range Begin.: start scale for the evaporation pressure transducer
reading;
Range Ending: end scale for the evaporation pressure transducer
reading;
Read Value: the value read, i.e. the measurement sent by the probe.
This screen, allows the reading of the pressure evaporating sensor
to be corrected if a difference between the measured value of the
sensor and the effective value is detected when measured with a
precision instrument. The maximum adjustment possible is between -
9.9°C and +9.9 °C.
The Read value is the measurement transmitted by the pressure
evaporating sensor which is already corrected.
This screen, allows the reading of the temperature evaporating
sensor to be corrected if a difference between the measured value of
the sensor and the effective value is detected when measured with a
precision instrument. The maximum adjustment possible is between -
9.9°C and +9.9 °C.
The Read value is the measurement transmitted by the temperature
evaporating sensor which is already corrected.
This screen is used to set:
Low Superheat: low superheat alarm activation delay time;
High Suct.Temp.: high suction temperature alarm activation delay
time;
LOP Failure: minimum operating pressure alarm activation delay time;
MOP Failure: maximum operating pressure alarm activation delay
time;
Press.Probe Failure After Compr. ON: pressure probe disconnected
or not working alarm activation delay time after the compressor starts;
Press.Probe Failure At Normal Work.: pressure probe disconnected
or not working alarm activation delay time in normal operation;