PART IV: MAINTENANCE
36
At least once a year carry out the maintenance operations listed below. In the case of seasonal servicing, it is recommended to carry
out the maintenance at the end of each heating season; in the case of continuous operation the maintenance is carried out every 6
months.
The replacement, adjustment and assembly of groups and/or components must be performed in the spaces provided during the instal-
lation phase and correct aeration of the rooms. Any operation must be carried out by qualified, trained and informed personnel, in com-
pliance with the Manufacturer's instructions and the regulations in force. For anything not expressly mentioned in this chapter, contact
the Manufacturer.The use of non original spare parts, any modification or even slight tampering, void the Warranty and release the
Manufacturer from any responsibility regarding the functionality of the system the burner has been installed in, and the safety of people
and/or property.
ROUTINE MAINTENANCE
Check that the gas meter is not moving when the burner is off. In case it is rotating, look for possible leaks.
Check the cleaning condition of the vent. Clean the vent by using exclusively a dry brush. If needed, disassemble it from the
motor’s shaft and wash it by using non corrosive detergents. Prior to disassemble the vent, take the measurements in relation to
the motor's shaft, so as to reassemble it in the same position.
Check that all parts in contact with combustive air (air box, protection mesh and Archimedean screw) are clean and free from any
obstruction that might impede free afflux. Clean it with compressed air if available and/or a dry brush or cloths. Eventually wash it
with non corrosive detergents.
Check the blast tube; it must be substituted in case of obvious cracks or anomalous holes. Slight deformations that do not affect
combustion may be tolerated
Check the condition of the burner-boiler gasket. Eventually substitute it.
Check the fan’s motor: no specific maintenance is needed. In case of anomalous noises when running, check the condition of the
bearings and eventually substitute them or completely substitute the motor.
Clean and examine the gas filter cartridge and replace it if necesssary;
Remove and clean the combustion head;
Examine and clean the ignition electrodes, adjust and replace them if necessary;
Examine and clean the detection electrode/photoelement (according to the burner models), replace it if necessary, in case of
doubt, check the detection circuit, after the burner start-up;
Clean and grease leverages and rotating parts.
At least every 2 months, or more often if needed, clean the room where the burner is installed.
Avoid leaving installations, papers, nylon bags, etc., inside the room. They could be sucked by the burner and cause malfunctio-
ning.
Check that the room’s vents are free from obstructions.
ATTENTION: Read carefully the “warnings” chapter at the beginnig of this manual.
WARNING: All operations on the burner must be carried out with the mains disconnected and the fuel manaul
cutoff valves closed!
ATTENTION! Any maintenance, cleaning or check intervals are a mere indication: the functionality of the burner -
and its components - depends, among other things, from capacity utilisation rate, environment, nature and qua-
lity of the fuels used.
ATTENTIONwhen servicing, if it was necessary to disassemble the gas train parts, remember to execute the gas
proving test, once the gas train is reassembled, according to the procedure imposed by the law in force.
PART IV: MAINTENANCE
Summary of Contents for C83X
Page 42: ......
Page 43: ......
Page 45: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023 ...
Page 52: ...8 Parameters level heating engineer ...
Page 94: ...50 ERROR CODE TABLE ...
Page 95: ...51 ...
Page 96: ...52 ...
Page 97: ...53 ...
Page 98: ...54 ...
Page 99: ...55 ...
Page 100: ...56 ...
Page 101: ...57 ...
Page 102: ...58 ...
Page 103: ...59 ...
Page 104: ...60 ...
Page 105: ...61 ...
Page 106: ...62 ...
Page 107: ...63 ...
Page 108: ...64 ...
Page 113: ......
Page 114: ......
Page 115: ......
Page 117: ...IG FU B ...
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......