PART III: INSTALLATION
20
Siemens VGD20.. e VGD40..
Componenti e posizione dei pressostati
Collegamento attuatore SKP2... alla rampa gas
Siemens SKP2.. (pressure governor)
- Connect the reference gas pipe (
TP
in figure; 8mm-external size pipe supplied loose), to the gas pressure nipples placed on the gas
pipe, downstream the gas valves: gas pressure must be measured at a distance that must be at least 5 times the pipe size.
- Leave the blowhole free (
SA
in figure). Should the spring fitted not permit satisfactory regulation, ask one of our service centres for a
suitable replacement.
- D: sede della molla di regolazione pressione.
version with SKP2 (built-in pressure stabilizer)Siemens VGD../VRD.. SKPx5 (Auxiliary-optional micro
switch)Gas valve
Se necessario il microinterruttore ausiliario (POC) deve essere ordinato un attuatore dedicato, diverso da quello solitamente fornito. Il
collegamento è mostrato in figura.
WARNING: removing the four screws BS causes the device to be unserviceable!
3
5
2
1
4
6
6
8
SKP15
SKP25
SKP15
SKP25
5
2
1
3
4
7
1
PGMIN pressostato gas di minima
2
PGMIN pressostato gas di minima (alternativo a 1)
3
PGCP pressostato gas controllo perdite
4
PGMAX pressostato gas di massima
5
Azionatore con stabilizzatore di pressione incorpo-
rato
6
Azionatore On-Off
7
Corpo valvola (Filettata)
8
Corpo valvola (Flangiata)
min. 5 Ø
Ø
TP
BS
SA
D
SKP2
Valve drive
AGA64 -
Plug connection
ON-OFF
End of stroke
End of stroke
Plug connection
(POC)
Valve
drive
AG
A64
Valve
drive
AG
A65
Summary of Contents for E115X
Page 45: ......
Page 46: ......
Page 47: ......
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......