PART III: OPERATION
35
The service level shows all the information about flame intensity, actuators position, number and lock codes:
1
.the first parameter will be “954”: the percentage of flame is shown on the right. By pr or - it is possible to scroll up/down the
parameter list.
2
Once the last parameter is accessed (143) by pressing
+
, the
End
message will blink.
3
PressPress
InFo
for more than three seconds or for more than three seconds orto return to the normal display.
For further nformation, see tha LMV2 related manual.
Parameter
Description
954
Flame intensity
121
% output, if set = automatic operation
922
Actuators position, 00=combustibile; 01= aria
161
Lock-outs number
701..725
Lock-outs History (see chapter 23 in the LMV2x manual)