PART I: SPECIFICATIONS
7
Technical Specifications
(*) NOTE ON THE BURNER WORKING SERVICE:
LMV2x automatically stops after 24h of continuous working. The device immedia-
telystarts up, automatically. LMV3x performs countinuous operation.
Gas categories and countries of application
Fuel
BURNER TYPE
E115X
M-..
E140X
M-..
E190X
M-..
E115X
L-..
E140X
L-..
E190X
L-..
Output
min. - max. kW
300 - 1.150 290 - 1.400 360 - 1.900 300 - 1.150 290 - 1.400 360 - 1.900
Fuel
Natural gas
LPG
Category
(see next paragraph)
I
3B/P
Gas flow rate
min.-max. Stm
3
/h
32 - 122
31 - 148
38 - 201
11,2 - 43
10,8 - 52
13,4 - 71
Gas pressure
min.-max. mbar
(see Note 2)
Power supply
230V 3~ / 400V 3N ~ 50Hz
Total power consumption
kW
2,7
2,7
3,5
2,7
2,7
3,5
Fan motor power consumption
kW
2,2
2,2
3,0
2,2
2,2
3,0
Protection
IP40
Approx. weight
kg
80 - 115
80 - 115
80 - 115
80 - 115
80 - 115
80 - 115
Operation
Progressive - Fully modulating
Valves size / Gas connection - 40
1"
1/2
/
Rp1
1/2
Valves size / Gas connection - 50
2"
/
Rp2
Valves size / Gas connection - 65
2"
1/2
/
DN65
Valves size / Gas connection - 80
3"
/
DN80
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service (*)
Intermittent
Note1:
All gas flow rates are referred to Stm
3
/ h (1.013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34,02 MJ / Stm
3
); for L.P.G. (net calorific value H
i
= 93,5 MJ / Stm
3
)
Note2:
Maximum gas pressure = 360 mbar (with
Dungs MBDLE)
= 500 mbar (with
Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure = see gas curves.
Note3:
Burners are suitable only for indoor operation with a maximum relative humidity of 80 %
GAS CATEGORY
COUNTRY
I
2H
AT, ES, GR, SE, FI, IE, HU, IS, NO, CZ, DK, GB, IT, PT, CY, EE, LV, SI, MT, SK, BG, LT, RO, TR, CH
I
2E
LU, PL
I
2E( R ) B
BE
I
2EK
NL
I
2ELL
DE
I
2Er
FR
DANGER! The burner must be used only with the fuel specified in the burner data
plate.
Type --
Model
--
Year --
S.Number --
Output --
Oil Flow
--
Fuel
--
Category --
Gas Pressure
--
Viscosity --
El.Supply --
El.Consump. --
Summary of Contents for E140X
Page 46: ......
Page 47: ......
Page 49: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 56: ...8 Parameters level heating engineer...
Page 98: ...50 ERROR CODE TABLE...
Page 99: ...51...
Page 100: ...52...
Page 101: ...53...
Page 102: ...54...
Page 103: ...55...
Page 104: ...56...
Page 105: ...57...
Page 106: ...58...
Page 107: ...59...
Page 108: ...60...
Page 109: ...61...
Page 110: ...62...
Page 111: ...63...
Page 112: ...64...
Page 117: ......
Page 118: ......
Page 119: ......
Page 121: ...IG FU B...
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......