PART III: OPERATION
33
call the Technical Service and tell the message data.
Cold start thermal shock (CSTP)
If the generator cannot suffer thermal shocks, the CSTP (Cold Start Thermal Schock) function can be enabled. This function is already
set by the Technical service (access by reserved password).
if this function is enabled, when the burner starts upthe “Thermal shock protection activated” message will be showed.
If this function is not enabled, after startup, the burner will rapidly increase the load according to the requested value and, if necessary,
to the maximum output.
Manual mode
To by-pass the thermal protection or not to let the buner operate in high flame stage (maximum output) after ignition, the manual mode
is provided.
To choose the manual mode (Manual Operation), use the SELECT arrow keys
Items to be set are the following:
SetLoad
: to set the required load percentage
set the required percentage and confirm by pressing ENTER; press ESC to exit.
choose “Autom/Manual/Off
three modes are provided:
Automatic
: automatic operation
Burner on
: manual operation
Burner off:
burner in stand-by
If the BurnerOn mode is choosen,the burner does not follow the modulator and probe settings, but operates at the set load.
For further details, see the LMV5x annexed manuals.
OperationalStat
Operation
ManualOperation
Params & Display
SetLoad
Autom/Manual/Off
SetLoad
Curr::
0.0%
New:
20.0%
SetLoad
Autom/Manual/Off
Autom/Manual/Off
Curr::
Automatic
New:
Burner On
Caution
: if BurnerOff mode is selected, the burner stays in stand-by.
Caution
: in the BurnerOn mode, the safety thresholds are set by the Technical Service.
Summary of Contents for E165A
Page 45: ......
Page 46: ......
Page 47: ......
Page 49: ...FRONTALE QUADRO FRONT CONTROL PANEL...
Page 50: ...FRONTALE QUADRO FRONT CONTROL PANEL...
Page 51: ......
Page 52: ......