PART III: OPERATION
37
Center head holes gas flow regulation
To adjust the gas flow, partially close the holes, as follows:
1
loosen the three
V
screws that fix the adjusting plate
D
;
2
insert a screwdriver on the adjusting plate notches and let it move CW/CCW as to open/close the holes;
3
once the adjustmet is performed, fasten the
V
screws.
4
The adjusting plate correct position must be regulated in the plant during the commissioning.
The factory setting depends on the type of fuel for which the burner is designed:
For natural gas burners, plate holes are fully opened
Center head holes gas flow regulation
To adjust the gas flow, partially close the holes, as follows:
1
loosen the three
V
screws that fix the adjusting plate
D
;
2
insert a screwdriver on the adjusting plate notches and let it move CW/CCW as to open/close the holes;
3
once the adjustmet is performed, fasten the
V
screws.
The adjusting plate correct position must be regulated in the plant during the commissioning.
The factory setting depends on the type of fuel for which the burner is designed:
For LPG burners, plate holes are opened about 1.7mm
V
D
closed holes
opened holes
V
D
closed holes
opened holes
Summary of Contents for E165A
Page 45: ......
Page 46: ......
Page 47: ......
Page 49: ...FRONTALE QUADRO FRONT CONTROL PANEL...
Page 50: ...FRONTALE QUADRO FRONT CONTROL PANEL...
Page 51: ......
Page 52: ......