PART I: SPECIFICATIONS
7
Technical Specifications
(*) NOTE ON THE BURNER WORKING SERVICE:
LMV2x automatically stops after 24h of continuous working. The device immedia-
telystarts up, automatically. LMV3x performs countinuous operation (with electrode only).
Gas categories and countries of application
(*) Premix type ...N burners are not enabled to work with these gas categories.
The above gas groups can be combined according to the standard EN437:2021 and national situation of countries.
BURNER TYPE
G258A
G335A
G380A
G400A
Output
min. - max. kW
165 - 2580
280 - 3350
295 - 3800
580 - 4000
Fuel
MG - Natural gas-Light oil
Category
(see next paragraph)
Gas rate- Natural gas
min.- max. (Stm
3
/h)
17,5 - 273
30 - 354
31 - 402
61 - 402
LPG rate
min.- max. (Stm
3
/h)
6,2 - 96
10,5 - 125
11 - 142
22 - 149
Gas pressure
mbar
(see Note 2)
Light oil rate
min. - max. kg/h
13,9 - 218
24 - 282
25 - 320
49 - 337
Light oil train inlet pressure
max. bar
2
Light Oil viscosity
cSt @ 40 °C
2 - 7,4
Light Oil density
kg/m
3
840
Power supply triphase
220 V/ 230 V 3~ / 380 V/ 400 V 3N ~ 50 Hz
Auxiliary Power supply
220 V/ 230 V 2~ / 220 V / 230 V 1N ~ 50 Hz
Total power consumption
kW
5,6
7,1
9,1
Pump motor
kW
1,1
1,1
1,1
Electric motor
kW
4,0
5,5
7,5
Protection
IP40
Operation
Progressive - Fully modulating
Gas train 50
Valves size / Gas connection
50 / DN50
Gas train 65
65 / DN65
Gas train 80
80 / DN80
Gas train 100
100 / DN100
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service
Intermitent
Note1:
All gas flow rates are referred to Stm
3
/ h (1.013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34,02 MJ / Stm
3
); for L.P.G. (net calorific value H
i
= 93,5 MJ / Stm
3
)
Note2:
Maximum gas pressure = 360 mbar (with
Dungs MBDLE)
= 500 mbar (with
Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure = see gas curves.
Note3:
Burners are suitable only for indoor operation with a maximum relative humidity of 80 %
Note4:
with electrode: for safety reasons the burner must stop automatically every 24 hours
Countries
Group
AL, AT, BE, BG, CH, CY, DE, DK, EE, ES, FI, FR, GB, GR, HR, HU,
IE, IS, IT, LT, LU, LV, MK, MT, NO, NL, PL, PT, RO, SE, SI, SK, TR
H
L (*)
E
2R (*)
EK (*)
Er (*)
LL (*)
E (R)
Summary of Contents for G335A
Page 53: ......
Page 54: ......
Page 55: ......
Page 57: ...Service manual AZL2x LMV2x 3x Burner Management System M12916CD Rev 3 4 03 2023...
Page 64: ...8 Parameters level heating engineer...
Page 106: ...50 ERROR CODE TABLE...
Page 107: ...51...
Page 108: ...52...
Page 109: ...53...
Page 110: ...54...
Page 111: ...55...
Page 112: ...56...
Page 113: ...57...
Page 114: ...58...
Page 115: ...59...
Page 116: ...60...
Page 117: ...61...
Page 118: ...62...
Page 119: ...63...
Page 120: ...64...
Page 125: ......
Page 126: ......
Page 127: ......