PART I: SPECIFICATIONS
7
Technical Specifications
Gas categories and countries of application
Fuel
BURNER TYPE
H365X M- H440X M- H500X M- H365X L- H440X L-
H500X L-
Output
min. - max. kW
650 - 3650
700 - 4400
580 - 5250
650 - 3650
700 - 4400
580 - 5250
Fuel
M -
Natural gas
L -
LPG
Category
(
see next paragraph
)
I3B/P
Gas rate
-
Natural gas
min.- max. (Stm
3
/h)
69 - 386
74 - 466
61 - 556
24 - 136
26 - 164
22 - 196
Gas pressure
mbar
(
see Note 2
)
(
see Note 2
)
Power supply
230V 3~ / 400V 3N ~ 50Hz
230V 3~ / 400V 3N ~ 50Hz
Total power consumption
kW
8
9,7
9,7
8
9,7
9,7
Electric motor
kW
7,5
9,2
9,2
7,5
9,2
9,2
Protection
IP40
IP40
Operation
MD -
Fully modulating
MD -
Fully modulating
Gas train
50
Valves size
/
Gas connection
50 / Rp 2
50 / Rp 2
Gas train
65
65 / DN65
65 / DN65
Gas train
80
80 / DN80
80 / DN80
Gas train
100
100 / DN100
100 / DN100
Operating temperature
°C
-10 ÷ +50
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
-20 ÷ +60
Working service*
Continuous
Continuous
Note1:
All gas flow rates are referred to Stm
3
/ h (1.013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34,02 MJ / Stm
3
); for L.P.G. (net calorific value H
i
= 93,5 MJ / Stm
3
)
Note2:
Maximum gas pressure = 360 mbar (with
Dungs MBDLE)
= 500 mbar (with
Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure = see gas curves.
Note3:
Burners are suitable only for indoor operation with a maximum relative humidity of 80 %
GAS CATEGORY
COUNTRY
I
2H
AT, ES, GR, SE, FI, IE, HU, IS, NO, CZ, DK, GB, IT, PT, CY, EE, LV, SI, MT, SK, BG, LT, RO, TR, CH
I
2E
LU, PL
I
2E( R ) B
BE
I
2EK
NL
I
2ELL
DE
I
2Er
FR
DANGER! The burner must be used only with the fuel specified in the burner data
plate.
Type --
Model
--
Year --
S.Number --
Output --
Oil Flow
--
Fuel
--
Category --
Gas Pressure
--
Viscosity --
El.Supply --
El.Consump. --
Summary of Contents for H365X
Page 46: ......
Page 47: ......
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......