29
Caution! In case it is necessary to immediately shut the burner down while working at high flame and the maximum load point is
not already set observing the combustion parameters, decrease gas by means of the pressure governor as to drive the burner to
a sufficient excess of air, then shut the burner down by the main switch.
At next start-up, start again with point P2 to the minimum load (factory-setting - see previous paragraph) and go on setting the
curve points.
ATTENTION: When the maximum load is reached (100%), check again the curve-points. The pressure at the governor has
changed and therefore also the gas flow rate to the other points. So, it is necessary to check the adjustment of the points
already set.
ATTENTION: for proper operation, it is necessary that the curve of each actuator does not reverse its slope.
ATTENTION: When % load value is changed by user, LMV recalculates all the curve-points according the new load value. It may
happen that the point you are adjusting, once saved, is moved to another position.
0
20
40
60
80
100
120
0
20
40
60
80
100
120
S
e
rv
omotor
a
nd V
S
D
pos
ition
Load [%]
Commissioned curve-points - example
Fuel
AIR
AUX3
VSD
Point Load 53,2
:5
Point Load 70
: 6
Fuel
53.1
O2 Air 65.5
VSD
90
Point Load 61,8
: 7
Fuel
53.1
O2 Air 65.5
VSD
90
Point Load 53,2
:5 Fuel
12
O2 Air 6.7
VSD
70
Point Load 61,8
: 6
Fuel
53.1
O2 Air 65.5
VSD
90
Point Load 70
: 7
Fuel
53.1
O2 Air 65.5
VSD
90
new order
position
P 1
P 1
P 2
P 3
P 4
P 5
P 6
P 7
P 8
P 9
P 1 0
Summary of Contents for H365X
Page 46: ......
Page 47: ......
Page 49: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 56: ...8...
Page 60: ...12 2 2 LMV5x program structure...
Page 87: ...39...
Page 94: ......
Page 95: ......
Page 96: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 98: ...Annex1 Example for motor cable...
Page 99: ......
Page 100: ...Annex 2 Example for sensor cable...
Page 101: ......
Page 102: ......
Page 106: ......