Rotation of fan motor and pump motor
Once the electrical connection of the burner is executed, remember to check the rotation of the motor. The motor should rotate according
to the indication on the body. In the event of wrong rotation, reverse the three-phase supply and check again the rotation of the motor.
NOTE: burners are supplied for three-phase 400V supply, and in the case of three-phase 230V supply it is necessary to modify
the electrical connections into the terminal box of the electric motor and replace the overload tripped relay.
Fig. 21: Power supply terminal board
IG: main switch
KM1: fan motor contactor
KM2: pump motor contactor
MP: pump motor
MV: fan motor
TP: pump motor thermal cutout
TV: fan motor thermal cutout
Fig. 22: Motors connectioni
CAUTION: adjust the thermal cut-out according to the motor rated current value.
Auxi
liary relais po
we
r s
upp
ly