C.I.B. UNIGAS - M03957CI
32
Calibration of air and gas pressure switches
Calibration of air pressure switch
To calibrate the air pressure switch, proceed as follows:
z
Remove the transparent plastic cap.
z
Once air and fuel setting have been accomplished, startup the burner.
z
During the pre-purge phase o the operation, turn slowly the adjusting ring nut
VR
in the clockwise direction (to increase the adju-
sting pressure) until the burner lockout, then read the value on the pressure switch scale and set it to a value reduced by 15%.
z
Repeat the ignition cycle of the burner and check it runs properly.
z
Refit the transparent plastic cover on the pressure switch.
Calibration of low gas pressure switch
As for the gas pressure switch calibration, proceed as follows:
z
Be sure that the filter is clean.
z
Remove the transparent plastic cap.
z
While the burner is operating at the maximum output, test the gas pressure on the pressure port of the minimum gas pressure
switch.
z
Slowly close the manual cutoff valve (placed upstream the pressure switch, see gas train installation diagram), until the detected
pressure is reduced by 50%. Pay attention that the CO value in the flue gas does not increase: if the CO values are higher than the
limits laid down by law, slowly open the cutoff valve as to get values lower than these limits.
z
Check that the burner is operating correctly.
z
Clockwise turn the pressure switch adjusting ring nut (as to increase the pressure value) until the burner stops.
z
Slowly fully open the manual cutoff valve.
z
Refit the transparent plastic cover on the pressure switch.
Adjusting the high gas pressure switch (when provided)
To calibrate the high pressure switch, proceed as follows according to its mounting position:
1
remove the pressure switch plastic cover;
2
if the maximum pressure switch is mounted upstreaam the gas valves: measure the gas pressure in the network, when flame is off;
by means of the adjusting ring nut
VR
, set the value read, increased by the 30%.
3
if the maximum pressure switch is mounted downstream the “gas governor-gas valves” group and upstream the butterfly valve:
light the burner, adjust it according to the procedure in the previous paragrph. Then, measure the gas pressure at the operating
flow rate, downstream the “gas governor-gas valves” group and upstream the butterfly valve; by means of the adjusting ring nut
VR
, set the value read on step 2, increased by the 30%;
4
replace the plastic cover.
Fully modulating burners
To adjust the fully-modulating burners, use the
CMF
switch on the burner control panel (see next picture), instead of the
TAB
thermo-
stat as described on the previous paragraphs about the progressive burners. Go on adjusting the burner as described before, paying
attention to use the CMF switch intead of
TAB
.
The
CMF
position sets the oprating stages: to drive the burner to the high-flame stage, set CMF=1; to drive it to the low-flame stage, set
CMF=2.
To move the adjusting cam set CMF=1 or 2 and then CMF=0.
The
air pressure switch
locks the control box if the air pressure is not the one requested. If it happens,
unlock the burner by means of the control box unlock pushbutton, placed on the burner control panel.
The
gas pressure switches
check the pressure to avoid the burner operate when the pressure value
is not in the requested pressure range.
VR
CMF
CMF = 0 stop at the current position
CMF = 1 high flame operation
CMF = 2 low flame operation
CMF = 3 automatic operation
Summary of Contents for HP60
Page 9: ...C I B UNIGAS M03957CI 9 Overall dimensions mm Boiler recommended drilling template ...
Page 49: ...C I B UNIGAS M03957CI 49 ...
Page 51: ...C I B UNIGAS M03957CI 51 WIRING DIAGRAM Cod 05 680 Progressive burners ...
Page 52: ...C I B UNIGAS M03957CI 52 WIRING DIAGRAM Cod 05 681 Fully modulating burners ...
Page 54: ......
Page 55: ......
Page 56: ......