4
SPECIFICATIONS
Note: all gas flow rates (Stm
3
/h) are referred to standard gas conditions: 1013 mbar pressure, 15 °C temperature.
Flow rates are referred to G20 natural gas (nett calorific value: 34.02 MJ/Stm
3
), if G25 is used (n.c.v.: 29.25 MJ/Stm
3
), flow rates
must be multiplied by 1.16 factor.
* Minimum pressure to get the maximum rate with any value of back pressure in combustion chamber. The burner operates cor-
rectly also with lower pressures but these must guarantee the needed rate.
BURNER MODEL IDENTIFICATION
Burners are identified by burner type and model. Burner model identification is described here following.
Type: HS5
Model:
LG.
PR.
S.
*.
A.
0.
40
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(1)
BURNER TYPE
(2)
FUEL
LG - L.P.G. / Light oil
(3)
OPERATION
Available versions
TN - Single stage
(4)
BLAST TUBE LENGHT
(see overall dimensions)
Available versions
S - Standard
L - Long
(5)
DESTINATION COUNTRY
* - see data plate
(6)
SPECIAL VERSIONS
A - Standard
(7)
EQUIPMENT
Available versions
0 - 2 Valves
1 - 2 leak detection monitor (on request if output < 1200 kW)
(8)
GAS TRAIN SIZE
(see specifications)
15= Rp1/2
20=Rp3/4
25= Rp1
BURNER MODEL
HS5
HS10
HS18
Output min.
kW
35
65
80
max. kW
70
140
200
Fuel
L.P.G.
Light oil
L.P.G.
Light oil
L.P.G.
Light oil
Category
I
3+
I
3+
I
3+
Gas rate min - max
Stm
3
/h
1.3 - 2.7
2.5 - 5.4
3 - 8
Light oil rate min - max
Kg/h
3 - 6
5.5 - 12
7 - 17
Gas pressure min.* - max.
mbar
20 - 200
20 - 200
20 - 200
Power supply - frequency
230 V - 50 Hz
230 V - 50 Hz
230 V - 50 Hz
Fan motor
kW
0.1
0.15
0.15
Pump motor
kW
0.1
0.1
0.1
Total power consumption
kW
0.25
0.25
0.25
Protection
IP40
IP40
IP40
Weight
Kg
20
27
27
Valves size
1/2”
3/4”
1”
Gas connection
Rp1/2
Rp3/4
Rp1
Operation
single stage
single stage
single stage
Destination country
*
*
*
PART I: INSTALLATION MANUAL