PART II: INSTALLATION
28
Connecting the burner to the oil pumping unit Suntec T+TV
Follow the scheme in the picture below to connect the burner to the oil pumping unit. The pump sends the oil coming from the tank to
the burner. The pressure governor makes the oil reach the nozzle at the required pressure, while the excess of oil goes back to the
tank. To change the delivery pressure act on the VRM adjusting screw of the pressure governor, reading the oil pressure at the nozzle
(put a pressure gauge on the oil lance manifold).
CAUTION
: caps are not sealing type but used for shipment only. The flexible hoses between the pump and the burner are the ones cal-
led (on the label) “Oil high pressure flexible hose”. The flexible hose called “Oil low pressure flexible hose” is the one to be connected
upstraem the oil filter.
VRM
to the burner
separated pumping unit
from the tank
to the tank
Summary of Contents for HTLX92R
Page 57: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 64: ...8...
Page 68: ...12 2 2 LMV5x program structure...
Page 95: ...39...
Page 102: ......
Page 103: ......
Page 104: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 106: ...Annex1 Example for motor cable...
Page 107: ......
Page 108: ...Annex 2 Example for sensor cable...
Page 109: ......
Page 110: ......
Page 114: ......