PART III: MAINTENANCE
51
MultiBloc MBE
MultiBloc VD Mounting
Removing the combustion head
1
Remove the top
H
.
2
Remove the
UV
detector out of its housing: disconnect electrode cables and the light oil flexible hoses.
3
Loosen the screws
V
holding the gas manifold
G
, loosen the connectors
E
.
4
Some models are provided with the
T
baffle. Move the gas manifold ahead and remove the baffle.
5
Pull out the complete group as shown in the picture below.
6
Clean the combustion head by means of a vacuum cleaner; scrape off the scale by means of a metallic brush.
Note:
to replace the combustion head, reverse the operations described above.
position
to push
1. Position VD on VB, fig. 2+3.
2. Slide VD forward up to the stop, fig. 4.
3. Screw VD on with 2 M5 screws for each, max. 5 Nm/44 in.-lb., fig. 5/6.
4. VD can be mounted rotated by 180°, fig. 7.
1
2
3
4
5
6
7
E
V
H
G
T
G