4
1 WIRING
RECOMMENDATIONS
1.1 Earthing
1.1.1 TN
earthing
system
For the LMV5x-System it is preconditioned that a TN earthing system is used.
In a TN earthing system, one of the points in the generator or transformer is connected with earth, usually the star point in a three-phase system.
TN
−
S: PE and N are separate conductors that are connected together only near the power source. This arrangement is the current standard for
most residential and industrial electric systems in North America and Europe.
TN-C-S: Combined PEN conductor from transformer to building distribution point, but with separate PE and N conductors in fixed indoor wiring.
LMV system must be connected to earth (PE).
∆
Volt must be 0 V between N-PE.
NOTE: PE = protection earth, it is not FE
FE = functional earth
1.1.2
Protective Earth (PE) and Functional Earth (FE)
P
rotective
E
arth (PE):
Known as an equipment grounding conductor, avoids hazards by keeping the exposed conductive surfaces of a device at earth potential.
To avoid possible voltage drop no current is allowed to flow in this conductor under normal circumstances, but fault currents will usually trip or blow
the fuse or circuit breaker protecting the circuit.
For example: burner body or the third wire in a 3 wire cable (N L E)
F
unctional
E
arth (FE):
Is not intended for shock protection. It is used for a common reference potential.
For example: cable shields.
N
PE
N
PE
TN-S-earthing
Generator or transformer
Earth
Consumer
TN-C-S-earthing
Generator or transformer
Earth
Consumer
L2
L3
L2
L3
L1
L1
Summary of Contents for HTLX92R
Page 57: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 64: ...8...
Page 68: ...12 2 2 LMV5x program structure...
Page 95: ...39...
Page 102: ......
Page 103: ......
Page 104: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 106: ...Annex1 Example for motor cable...
Page 107: ......
Page 108: ...Annex 2 Example for sensor cable...
Page 109: ......
Page 110: ......
Page 114: ......