3 Thermostatic series and safety loop
The burner shuts down properly when the thermostatic series (X5-03.1 and X5-03.4 - terminals 3 and 4 of the burner terminal block) opens. In this way,
before shut-down, the burner drives to the minimum load, then the fuel valve will close. The post-purging phase will be performed if set. By re-closing the
thermostatic series, the burner will start-up again.
In the plant other safety devices are provided (levels, pressure switches, thermostats, air damper) . All these contacts are connected in series to the 318-
319 terminals of the burner supply terminal block. When the safety loop closes, the burner is ready to restart. The actuators move to "home position"
(standby position), and if terminals 3-4 are closed the start-up cycle resumes; otherwise the burner enters the standby phase.
In the plant the safety thermostat is provided as well. If this thermostat switches (terminals X3-04.1 e X3-04.2 corresponding to terminals 318 and 319 of
the burner supply terminal block - see below), the system will lead to an immediate burner lockout.
In case of burner designed with automatic pull-out system from the generator, the burner flange end switch is connected to terminalsX3-03.1 e X3-03.2.
If the contact open, the burner automatically shuts down.
NOTE:
When the safety loop opens, the burner will immediately turns off, skipping the low flame stage. It's important to distinguish between "safety
loop" and "thermostatic series"
The maximum number of emergency shut-downs is 16. When this number is reached a lockout will occur AZL will show the message: “Open safety
loop”.
Following the below route access to the programming levels of the menu:
1st level
2nd level
3rd level
4th level
5th level
6th level
Description
Params & Display
Menu level for making the parameter
settings
BurnerControl
Setting
the
burner
control
parameters
Configuration
RepetitCounter
It sets the maximum number of possible
repetitions
SafetyLoop
1...16
Default is set on 16
Keys:
SLT: safety loop thermostat
AUX: auxiliary contact
Water Shortage: water flow switch
Remove the bridge
Connect to the safety loop
Summary of Contents for HTLX92R
Page 57: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 64: ...8...
Page 68: ...12 2 2 LMV5x program structure...
Page 95: ...39...
Page 102: ......
Page 103: ......
Page 104: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 106: ...Annex1 Example for motor cable...
Page 107: ......
Page 108: ...Annex 2 Example for sensor cable...
Page 109: ......
Page 110: ......
Page 114: ......