19
ExtLC X5-03
= three-point external controller (X5-03 terminals)
Int LC
= internal controller (LMV5x) (it switches between 2 set points, W1,W2 set thought AZL. the switch from W1 and W2 is realized opening/closing
the LMV5x... terminals X62.1, X62.2).
Int LC Bus
= internal controller and set point setting via bus connection
Int LC X62
= internal controller (LMV), but set point is externally controlled by means of a voltage/current signal on X62 terminals
Ext LC X62
= external controller, the burner output is controlled by means of a voltage/current signal on X62 terminals
Ext LC Bus
= external controller, the burner output is controlled via bus
ATTENTION: in case of FGR, it is not possible to connect a modulating temperature probe at the X60 door of the LMX5...
See the proper chapter for configuration.
6 Setting the probes and set-points
If the LMV5x internal load controlled is used, a temperature or pressure probe can be connected to the terminal X60 or X61. In this case, set the type of
probe and its operating range.
6.1
Configuration of a temperature probe at X60 door
ATTENTION: If the external load controller is set do not connected to terminals X60 or X61.
ATTENTION: If the burner is equipped with FGR with temperature compensation a Pt1000 must be set.
ATTENTION: Depending on the sensor, the value is visualized as °C or bar.
Following the below route access to the programming levels of the menu by means the Esc
1st level
2nd level
3rd level
4th level
5th level
6th level
Description
Params & Display
Menu level for making the parameter
set- tings
LoadController
Settings for the internal load controller
Configuration
General configuration of the load
controller
Sensor Select
Select actual value input
Pt100
Ni1000
Temp sensor
Press sensor
Pt100Pt1000
Pt100Ni1000
NoSensor
See the table below for the meaning of
the choice.
Possible settings are:
Probe Description
Pt100
Temperature sensor Pt100 at the input X60, internal temperature limiter function = activated
Pt1000
Temperature sensor Pt1000 at the input X60, internal temperature limiter function = activated
Ni1000
Temperature sensor LG-Ni1000 at the input X60, internal temperature function = activated
TempSens Temperature sensor at the input X61, internal temperature switch function = deactivated
PressSens Pressure sensor at the input X61, internal temperature switch function = deactivated
Pt100
Pt1000
Temperature sensor Pt100 at input X60 for temperature controller and temperature limiter function and temperature sensor Pt1000 at input
X60 additionally for temperature limiter function
Pt100
Ni1000
Temperature sensor Pt100 at input X60 for temperature controller and temperature limiter function and temperature sensor LG-Ni at input
X60 additionally for temperature limiter function.
No Sensor No actual value sensor (e.g. in the case of external predefined loads and without internal temperature limiter).
ATTENTION: If a boiler second probe is to be connected to terminals (1000 Ohm only), internal functions TL_ThreshOff and
DiffIntervTL_SD_On are activated automatically (see paragraph SETTING FUNCTIONS “TL_ThreshOff” AND “TL_SD_On”).
Summary of Contents for HTLX92R
Page 57: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 64: ...8...
Page 68: ...12 2 2 LMV5x program structure...
Page 95: ...39...
Page 102: ......
Page 103: ......
Page 104: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 106: ...Annex1 Example for motor cable...
Page 107: ......
Page 108: ...Annex 2 Example for sensor cable...
Page 109: ......
Page 110: ......
Page 114: ......