26
9 ADJUSTING THE AIR/FUEL RATIO CURVES
ATTENTION: when burners are provided with VSD, before setting the air/fuel ratio curves, the Standardization of the motor
speed must be performed (see chapter “Standardization”).
1st level
2nd level
3rd level
4th level
5th level
6th level
Description
Params & Display
Menu level for making the
parameter settings
RatioControl
Parameter settings for fuel/
air ratio control
GasSettings
OilSettings
Parameter settings for firing
on gas or on oil
CurveParams
9.1
Fuel burner settings - curve-points
Two curve points are factory set (default settings) corresponding to a hypothetic low flame stage
Note:
points P1 and P2, are temporally mentioned 10% and 100% load, independently from the actual load. The operator can name the load on each point,
without respecting the actual load value in that point. LMV5x will order those points automatically according to the load values set by the operator.
With this setting, by closing the thermostat series, the burner drives to minimum load position
P1
, after ignition. Then it drives to position
P2
without
increasing the output, as both the points are set with actuators minimum opening.
ATTENTION: For burners with FGR and LMV52.400, the parameter is set to "deactivated".
0
20
40
60
80
100
120
0
20
40
60
80
100
120
S
e
rv
omotor
a
nd V
S
D
pos
ition
Load [%]
Factory set curve-points
Fuel
AIR
AUX3
VSD
P 2
P 1
Summary of Contents for HTLX92R
Page 57: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 64: ...8...
Page 68: ...12 2 2 LMV5x program structure...
Page 95: ...39...
Page 102: ......
Page 103: ......
Page 104: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 106: ...Annex1 Example for motor cable...
Page 107: ......
Page 108: ...Annex 2 Example for sensor cable...
Page 109: ......
Page 110: ......
Page 114: ......