23
Checking the detection current
To measure the detection signal follow the diagram on the next picture.
If the signal is not in the advised range, check the electrical contacts, the cleaning of the combustion head, the position of the photore-
sistor and if necessary replace it.
Seasonal stop
To stop the burner in the seasonal stop, proceed as follows:
1
turn the burner’s main switch to 0 (Off position)
2
disconnect the power mains
3
close the fuel cock of the supply line
Burner’s disposal
In case of disposal, follow the instructions according to the laws in force in your country about the “Disposal of materials”.
Fig. 27
Minimum current intensity with flame
65 µA
Maximum current intensity without flame
5 µA
Maximum possible current intensity with flame
200 µA
1
2
SCALE µA DC
CONNECTOR CN7