21
Immersion or strap-on sensors
Immersion probes installation
Sensors must be installed on the stretch of pipe in which fluid circula-
tes all the time.
The rigid stem (sensing element doing the measuring) must be inser-
ted by at least 75mm and must face the direction of flow.
Recommended locations: on a bend or on a straight stretch of pipe
but tilted by 45° and against the flow of fluid.
Protect them to prevent water from infiltrating (dripping gates, conden-
sation from pipes etc.) .
Installing QAD2.. strap-on sensors
Make sure fluid is circulating in the chosen location.
Eliminate insulation and paintwork (including rust inhibitor) on a min.
100mm length of pipe.
Sensors come with straps for pipes up to 100 mm in diameter .
Placing the probes (QAD22.../QAE21.../QAP21.../RCA...)
With pumps on outlet
with 3 ways valves / with 4 ways valves
Panel system / burner control
With pumps on return
with 3 ways valves / with 4 ways valves
Strap-on or immersion sensors?
QAD2.. strap-on sensors
Advantages :
z
10 sec. time constant
z
Installed with system running (no plumbing work)
z
Installation can be changed easily if it proves incorrect
П
Limits:
z
Suitable for pipe diameters max. 100 mm
z
Can be affected by currents of air etc.
QAE2... immersion sensors
Advantages:
z
Measure "mean" fluid temperature
z
No external influence on measurement such as: currents of air,
nearby pipes etc.
Limits:
z
Time constant with sheath: 20 sec.
z
Hard to change installation position if it proves incorrect
Summary of Contents for KTP1030
Page 25: ...C I B UNIGAS M039207CB 25 Fig 17 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 46: ...C I B UNIGAS M039207CB 46...
Page 47: ...C I B UNIGAS M039207CB 47...
Page 48: ...C I B UNIGAS M039207CB 48...
Page 49: ...C I B UNIGAS M039207CB 49...
Page 50: ...C I B UNIGAS M039207CB 50 Pumping Unit Electric Wiring Diagrams...
Page 51: ...C I B UNIGAS M039207CB 51...
Page 52: ...C I B UNIGAS M039207CB 52...
Page 55: ...C I B UNIGAS M039207CB 55...
Page 59: ......
Page 74: ......
Page 83: ......
Page 84: ......
Page 85: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 100: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 101: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 102: ...M12927CA MOUNTING 2...
Page 118: ...1 RWF55 5X RWF55 6X User manual M12926CA Rel 0 1 10 2015...
Page 119: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Page 140: ......
Page 141: ...23 Note Specifications and data subject to change Errors and omissions excepted...