3
Set up for temperature probe Pt100 for high temperature (350°C max.)
Verify wiring of the sensor
Regulation of the set-point =
80
It can be modified by using arrows "up" and "down".
By pushing
F
you go to parameters:
Hy.P
10 (hysteresis positive for output 1 terminals 21-22 (ex Q13-Q14)
Hy.n
-5 (hysteresis negative for output 1 terminals 21-22 (ex Q13-Q14)
Keep pushing
F
until you see
PASS
, release
F
and through the arrows set
99
, push
F
and visualize
Pro
(protection code) default is
12
, through the arrows set
128
and push
F,
keep it pushed until all parameters
InF
,
CFG
,
InP
,
Out
,
PASS
are visualized.
CFG
S.tun 0
hPb
1,2
hIt 5,83
hdt
1,33
…
InP
….
tyP
30 (Pt100)
…
dP_S
1 (decimals num.)
Lo.S
0 (min. sensor scale)
Hi.S
850,0 (max sensor scale)
oFS
0 (offset of input correction)
Lo.L
0,0 (lower set-point range limit)
Hi.L
350,0 (upper set-point range limit)
Summary of Contents for KTP1030
Page 25: ...C I B UNIGAS M039207CB 25 Fig 17 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 46: ...C I B UNIGAS M039207CB 46...
Page 47: ...C I B UNIGAS M039207CB 47...
Page 48: ...C I B UNIGAS M039207CB 48...
Page 49: ...C I B UNIGAS M039207CB 49...
Page 50: ...C I B UNIGAS M039207CB 50 Pumping Unit Electric Wiring Diagrams...
Page 51: ...C I B UNIGAS M039207CB 51...
Page 52: ...C I B UNIGAS M039207CB 52...
Page 55: ...C I B UNIGAS M039207CB 55...
Page 59: ......
Page 74: ......
Page 83: ......
Page 84: ......
Page 85: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 100: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 101: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 102: ...M12927CA MOUNTING 2...
Page 118: ...1 RWF55 5X RWF55 6X User manual M12926CA Rel 0 1 10 2015...
Page 119: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Page 140: ......
Page 141: ...23 Note Specifications and data subject to change Errors and omissions excepted...