7
ConF > OutP (parameter under group only for RWF50.3)
Parameter Value
Description
FnCt
tipo di controllo
1
4
1 = analog input 1 doubling with possibility to convert
(depending on par
SiGn
)
4 = modulation controller
SiGn
type of output signal
0
1
2
physical output signal (terminals A+, A-)
0 = 0÷20mA
1 = 4÷20mA
2 = 0÷10V
rOut
Value when out of
input range
0
…101
signal (in percent) when measurement range is crossed
oPnt
zero point
-1999…
0
..+9999
value range of the output variable is assigned to a physical
output signal Per default, the setting corresponds to 0...100%
angular positioning for the controller outputs (terminals A+, A-)
(effective only with
FnCt
= 1)
End
End value
-1999…
100
..+9999
value range of the output variable is assigned to a physical
output signal Per default, the setting corresponds to 0...100%
angular positioning for the controller outputs (terminals A+, A-)
(effective only with
FnCt
= 1)
(
bold
= factory settings)
ConF > binF
Parameter Value
Description
bin1
digital inputs
(terminals DG - D1)
0
1
2
4
0 = without function
1 = set-point changeover (SP1 / SP2)
2 = set-point shift (
Opr
>
dSP
parameter = value of set-point
modify)
4 = changeover of operating mode
open – modulating operation;
close – 2 stage operation.
(
bold
= factory settings)
ConF > dISP
Parameter Value
Description
diSU
upper display
(red)
0
1
4
6
7
display value for upper display:
0 = display power-off
1 = analog input value
4 = Controller’s angular positioning
6 = set-point value
7 = end value with thermal shock protection
diSL
lower display
(green)
0
1
4
6
7
display value for lower display:
0 = display power-off
1 = analog input value
4 = Controller’s angular positioning
6 = set-point value
7 = end value with thermal shock protection
tout
timeout 0..
180
..250
time (s) on completion of which the controller returns
automatically to the basic display, if no button is pressed
dECP
decimal point
0
1
2
0 = no decimal place
1 = one decimal place
2 = two decimal places
CodE
level lockout
0
1
2
3
0 = no lockout
1 = configuration level lockout (ConF)
2 = Parameter and configuration level lockout (PArA & ConF)
3 = keyboard lockout
(
bold
= factory settings)
Summary of Contents for KTP1030
Page 25: ...C I B UNIGAS M039207CB 25 Fig 17 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 46: ...C I B UNIGAS M039207CB 46...
Page 47: ...C I B UNIGAS M039207CB 47...
Page 48: ...C I B UNIGAS M039207CB 48...
Page 49: ...C I B UNIGAS M039207CB 49...
Page 50: ...C I B UNIGAS M039207CB 50 Pumping Unit Electric Wiring Diagrams...
Page 51: ...C I B UNIGAS M039207CB 51...
Page 52: ...C I B UNIGAS M039207CB 52...
Page 55: ...C I B UNIGAS M039207CB 55...
Page 59: ......
Page 74: ......
Page 83: ......
Page 84: ......
Page 85: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 100: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 101: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 102: ...M12927CA MOUNTING 2...
Page 118: ...1 RWF55 5X RWF55 6X User manual M12926CA Rel 0 1 10 2015...
Page 119: ...2 DEVICE INSTALLATION Fixing system Drilling dimensions...
Page 140: ......
Page 141: ...23 Note Specifications and data subject to change Errors and omissions excepted...