5
hi ld
1.2
.Frequency inverter / Variable Speed Drive (VSD)
A VSD is one of the strongest EMC sources in a boiler house, so the following is recommended:
Use only VSD with EMC- filter!
Cable from VSD to the fan motor (Line voltage)
Use a complete separate and shielded cable from the VSD to the fan motor! Connect the shield at VSD- and at the motor- side with PE.
Details and further information see related VSD- documentation.
Cable from LMV5 to VSD (Low voltage)
Use a shielded cable from LMV5 to VSD. The shield of this cable has to be connected only at LMV5 side with X73.6 (FE), not at the VSD side:
1.3
Ignition electrodes and transformers
The Ignition is also one of the strong EMC sources, so the following is recommended:
•
Keep the cable loop/length in the high voltage ignition circuit as short as possible.
•
Use
special
EMC-ignition
cable
•
Avoid capacitive and inductive coupling to other signal paths.
•
Use separate wiring for the ignition high voltage cable, with max. possible distance to other cables and to the burner housing.
•
e.g.: use a electrical insulating conduit or distance parts (e.g. plastic material), see also Appendix "Example for wiring, earthing and
shielding the LMV5-System"
•
Prefer a double pole ignition (see drawings below).
•
When using a double probe ignition, the cables should be run close together to ensure that the area of emissions is as small as possible.
Double pole ignition: recommended
If a single pole ignition must be used
, it is very important to have a low impedance at the mechanical connections (no insulation material, e.g.
paint), because than you get a
good
current path from the ignition spark back to the ignition transformer, that results in
low
EMC-emissions:
If you have high impedance at the mechanical connections, e.g. caused by paint, you get
bad
multiple current paths from the ignition spark back to
the ignition transformer, that results in
high
EMC-emissions
High
Voltage
ignition
trasformer
VS
Earth
Note
: If the LMV5 is mounted in a cabinet, alternative to
(X73.6 / FE), also a connection with the PE- rail in the
cabinet is possible
LMV5
VSD
gas train
Low impedance, no
electrical insulating
material (e.g. paint)
LMV5x
Current path
back to
ignnition
trasformer
Summary of Contents for N880X
Page 41: ......
Page 42: ......
Page 43: ......
Page 45: ...Siemens LMV5x Service Manual M12920CC rev 2 1 08 2017...
Page 52: ...8...
Page 56: ...12 2 2 LMV5x program structure...
Page 83: ...39...
Page 90: ......
Page 91: ......
Page 92: ...Note Specifications and data subject to change Errors and omissions excepted...
Page 94: ...Annex1 Example for motor cable...
Page 95: ......
Page 96: ...Annex 2 Example for sensor cable...
Page 97: ......
Page 98: ......
Page 102: ......
Page 113: ...QF A QF B...
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ...SQM4x AIR SQM4x GAS...
Page 120: ...QF A QF B...
Page 121: ......
Page 122: ......