Oil pumps
PN91: SUNTEC TA2 / DANFOSS KSM50
PN92/93/510: SUNTEC TA3 / DANFOSS KSM70
PN515: SUNTEC TA4 / DANFOSS KSM100
PN520/525: SUNTEC TA5 / DANFOSS KSM140
Keys
1
Pressure regulator
2
Pressure/Vacuum gauge port to measure inlet pressure/vacuum
3
Pressure gauge port
5
Suction
7
To the nozzle
8
Return
1
Inlet G1/2
2
To the nozzle G1/2
3
Return G1/2
4
Pressure gauge port G1/4
5
Vacuum gauge port G1/4
6
Pressure governor
About the use of fuel pumps
z
Make sure that the by-pass plug is not used in a single pipe installation, because the fuel unit will not function properly and damage
to the pump and burner motor could result.
z
Do not use fuel with additives to avoid the possible formation over time of compounds which may deposit between the gear teeth,
thus obstructing them.
z
After filling the tank, wait before starting the burner. This will give any suspended impurities time to deposit on the bottom of the
tank, thus avoiding the possibility that they might be sucked into the pump.
z
On initial commissioning a "dry" operation is foreseen for a considerable length of time (for example, when there is a long suction
line to bleed). To avoid damages inject some lubrication oil into the vacuum inlet.
z
Care must be taken when installing the pump not to force the pump shaft along its axis or laterally to avoid excessive wear on the
joint, noise and overloading the gears.
z
Pipes should not contain air pockets. Rapid attachment joint should therefore be avoided and threaded or mechanical seal junc-
tions preferred. Junction threads, elbow joints and couplings should be sealed with removable sg component. The number of junc-
tions should be kept to a minimum as they are a possible source of leakage.
z
Do not use PTFE tape on the suction and return line pipes to avoid the possibility that particles enter circulation. These could depo-
sit on the pump filter or the nozzle, reducing efficiency. Always use O-Rings or mechanical seal (copper or aluminium gaskets) jun-
ctions if possible.
z
An external filter should always be installed in the suction line upstream of the fuel unit.
Danfoss KSM..
Oil viscosity
2.5 ÷ 450 cSt
Oil temperature
-10 ÷ 160 °C
Max. suction pressure
4 bar
Min. suction pressure
-0.45 bar to avoid gasing
Max. return pressure
4 bar
Rotation speed
3450 rpm max
Suntec TA..
Oil viscosity
3 ÷ 75 cSt
Oil temperature
0 ÷ 150°C
Min. suction pressure
- 0.45 bar to avoid gasing
Max. suction pressure
5 bar
Max. return pressure
5 bar
Rotation speed
3600 rpm max.