PART I: SPECIFICATIONS
7
* NOTE ON THE WORKING SERVICE: the control box automatically stops after 24h of continuous working. The control box
immediately starts up, automatically.
1.3 Country and usefulness gas categories
BRUCIATORE TIPO
R1025
L-.....1.xx
R1030
L-....1.65
R1030
L-....1.xx
R1040
L-.....1.xx
Output
min - max kW
2550 - 8700
2550 - 9500
2550 - 10600
2550 - 13000
Fuel
L -
LPG
Gas category
I
3B/P
Gas rate
min.-max. (Stm
3
/h)
95 - 325
95 - 355
95 - 396
270 - 485
Power supply
400V 3N~ 50
400V 3N~ 50
400V 3N~ 50
400V 3N~ 50
Total power consumption
kW
19
22.5
22.5
30.5
Electric motor
kW
18.5
22
22
30
Protection
IP40
Operation
Progressive - Fully modulating
Pressure
(see Note 2)
Gas train 65
ØValves Connection
2”
1/2
/ DN65
2”
1/2
/ DN65
2”
1/2
/ DN65
-
Gas train 80
ØValves Connection
3” / DN80
3” / DN80
3” / DN80
3” / DN80
Gas train 100
ØValves Connection
4” / DN100
4” / DN100
4” / DN100
4” / DN100
Gas train 125
ØValves Connection
-
-
-
5” / DN125
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service*
Intermitent
Note1:
All gas flow rates are referred to Stm
3
/h (1013 mbar absolute pressure, 15 °C temperature) and are valid for G20 gas
(net calorific value H
i
= 34.02 MJ/Stm
3
); for L.P.G. (net calorific value H
i
= 93.5 MJ/Stm
3
)
Note2:
Maximum gas pressure = 500mbar (with
Siemens VGD)
Minimum gas pressure = see gas curves.
GAS
CATEGORY
COUNTRY
I
2H
AT ES GR SE
FI
IE
HU
IS
NO CZ DK GB
IT
PT CY EE LV
SI
MT SK BG LT RO TR CH
I
2E
LU
PL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2E( R ) B
BE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2L
NL
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2ELL
DE
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
I
2Er
FR
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-