Adjust this thermostat to the correct value according to the
viscosity-temperature diagram and check the temperature by
using a thermometer with a scale of up to 200° C mounted on
the pre-heating tank.
Safety resistors thermostat TRS:
it is factory preset and
sealed. Don not modify it!
When the set temperature is exceeded, check the reason and
reset it by means of the push button PR
Resistor thermostat TR:
check the best atomising oil tempe-
rature and set it on TR.
Thermostat TCN
(it gives the enabling signal to the oil N.C.
valve): set TCN at about 20° less than TR.
Fig. 18 - Probe connections (Danfoss MCX)
PR
Pb3
Pb1
TR
Pb4
TCN - TRS