PART II: INSTALLATION
20
BURNERS WITH INVERTER VARIANT (if provided)
The manufacturer provides:
KOSTAL
: on-board or wall-mounted (in the latter case the kit is required)
DANFOSS
: wall-mounted
Both can be equipped with a braking resistor.
The burner terminal box is prepared to receive certain signals (for connection to the inverter, see the dedicated connection diagram).
The
LMV51.300 / LMV52.xxx, HAGC31-CU01 e LMV37.400/LMV26.300
electronic cam burners with fan motor driven by inverter in
addition to the air and fuel adjustment curves also have a fan motor speed adjustment curve.
Generally the curve of the inverter goes from 50% to 100% of the engine revolutions. This, in addition to improving the setting of the
burner also allows a saving on the consumption of the fan engine.
Terminal interface with Inverter
Input signals for the inverter depending on the equipment:
LMV51.300 / LMV52.xxx
4÷20mA
HAGC31-CU01
4÷20mA
LMV37.400 / LMV26.300
0÷10V
DANFOSS FC101
DANFOSS FC102
INVEOR M
LMV5
LMV2x/3x
- HAGC31-CU01
Braking resistances
possibility of use only for
FC102
possibility of use
only for
INVEOR