PART I: SPECIFICATIONS
7
Technical Specifications
Gas categories and countries of application
BURNER TYPE
TLX2020
TLX2030
TLX2040
Output
min - max kW
2000 - 16000
2400 - 20000
3900 - 31500
Fuel
Natural gas
Category
(see next paragraph)
Gas rate
min.-max. (Stm3/h)
212 - 1693
254 - 2116
413 - 3333
Gas pressure
Pressure
(see Note 2)
Controls power supply
230
V
/ 400
V
50
Hz
Controls power consumption
kW
0,5
Protection
IP54
Operation
MD - Fully modulating
Gas train
Valves size / Gas connection
80 / DN80
-
-
100 / DN100
100 / DN100
-
125 / DN125
-
150 / DN150
150 / DN150
Operating temperature
°C
-10 ÷ +50
Storage Temperature
°C
-20 ÷ +60
Working service
Continuous
Note1:
All gas flow rates are referred to Stm
3
/ h (1.013 mbar absolute pressure, 15° C temperature) and are valid for G20 gas
(net calorific value H
i
= 34,02 MJ / Stm
3
= 9,45 kWh / Stm
3
);
Note2:
Maximum gas pressure= 500 mbar (with
Siemens VGD or Dungs MultiBloc MBE)
Minimum gas pressure= see gas curves.
Warning:
Burners are suitable only for indoor operation with a maximum relative humidity of 80%
GAS CATEGORY
COUNTRY
I
2H
AT, ES, GR, SE, FI, IE, HU, IS, NO, CZ, DK, GB, IT, PT, CY, EE, LV, SI, MT, SK, BG, LT, RO, TR, CH
I
2E
LU, PL
I
2E( R ) B
BE
I
2EK
NL
I
2ELL
DE
I
2Er
FR