Submenu
REG – regulation parameters group :
Menu Parameter
Description
Additional
description
Min
Max
Default U.M.
Visibility
condition Level
Modbus
index
REG
REGULATION
0
Pb1
Probe 1
0
rES
Set-point Probe 1
(Tank resistor)
Don't modify it
-50,0
200,0
0,0
°C
3
42
AL1
Probe 1 - Low Temperature Alarm
Threshold
Don't modify it
-50,0
200,0
-50,0
°C
3
43
AH1
Probe 1 - High Temperature Alarm
Threshold
Don't modify it
-50,0
200,0
200,0
°C
3
44
d01
Probe 1 differential
0,0
20,0
3,0
°C
3
45
Pb2
Probe 2
0
tCI
Set-point Probe 2
(Plant Consent)
Plant consent according to table
“
Set point adjustment
”
-50,0
200,0
120,0
°C
0
46
AL2
Probe 2 - Low Temperature Alarm
Threshold
Don't modify it
-50,0
200,0
-50,0
°C
2
47
AH2
Probe 2 - High Temperature Alarm
Threshold
Don't modify it
-50,0
200,0
200,0
°C
2
48
d02
Probe 2 differential
0,0
20,0
3,0
°C
2
49
Pb3
Probe 3
0
rE3
Type of regulation of probe 3
(Oil tank exit)
Type of regulation
0= thermostat; 1= PID (don't modify)
0
1
1
3
50
OIL
Set-point Probe 3 (Oil tank exit)
Nozzle oil temperature according to the
table “
Set point adjustment
”
-50,0
200,0
130,0
°C
0
51
AL3
Probe 3 - Low Temperature Alarm
Threshold (Oil tank exit)
Don't modify it
-50,0
200,0
-50,0
°C
2
52
AH3
Probe 3 - High Temperature Alarm
Threshold (Oil tank exit)
Don't modify it
-50,0
200,0
200,0
°C
2
53
Pb3
Proportional band for PID Probe 3
(Oil tank exit)
Proportional band for first PID regulation
0,0
200,0
60,0
3
54
db3
Dead Zone for PID Probe 3
(Oil tank exit)
Dead zone for first PID regulation
0,0
20,0
0,0
°C
rE3 =1
3
55
rt3
Integral Time (Ti) for PID Probe 3
(Oil tank exit)
Integral time for first PID regulation
0,0
1000,0
120,0
s
rE3 =1
3
56
dt3
DerivativeTime (Td) for PID Probe 3
(Oil tank exit)
Derivative time for first PID regulation
(~ ¼ di rt3)
0,0
300,0
30,0
s
rE3 =1
3
57
db3
Dead Zone for PID Probe 3
(Oil tank exit)
Dead zone for first PID regulation
0,0
20,0
0,0
°C
rE3 =1
3
55
COD. M12924CA Rel. 0.5 03/2016
Summary of Contents for TN90
Page 2: ......
Page 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 34: ...CIB UNIGAS M039259CA 34...
Page 54: ......
Page 63: ......
Page 64: ......
Page 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 82: ...M12927CA MOUNTING 2...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......