COD. M12924CA Rel. 0.5 03/2016
Menu Parameter
Description
Additional
description
Min
Max
Default U.M.
Visibility
condition Level
Modbus
index
pi1
Overshooting for Integral action
(Oil tank exit)
Don't modify it
100
1000
200
rE3 =1
3
58
pi2
Derivative action enabling
(Oil tank exit)
Don't modify it
0
1
1
rE3 =1
3
59
pi3
Filtering factor for derivative action
(Oil tank exit)
Don't modify it
1
100
20
rE3 =1
3
60
pi4
Duty cicle PWM for output DO3
and/or AO1 (0-10V)
Don't modify it
1
300
5
s
rE3 =1
3
61
SL3
Output selection DO3 and/or AO1
(0-10V)
Digital selection output for control
thyristors; Don't modify it
0
2
AO1
3
62
p21
Proportional band for PID Probe 1
(Tank resistor)
Proportional band for second PID
regulation
0,0
200,0
50,0
rE3 =1
3
63
p22
Dead Zone for PID Probe 1
(Tank resistor)
Dead zone for second PID regulation
0,0
20,0
0,0
°C
rE3 =1
3
64
p23
Integral Time (Ti) for PID Probe 1
(Tank resistor)
Integral time for second PID regulation
0,0
1000,0
110,0
s
rE3 =1
3
65
p24
DerivativeTime (Td) for PID Probe 1
(Tank resistor)
Derivative time for second PID regulation
0,0
300,0
23,0
s
rE3 =1
3
66
p25
Overshooting for Integral action
(Tank resistor)
Don't modify it
100
1000
200
rE3 =1
3
67
p26
Derivative action enabling
(Tank resistor)
Don't modify it
0
1
1
rE3 =1
3
68
p27
Filtering factor for derivative action
(Tank resistor)
Don't modify it
1
100
20
rE3 =1
3
69
p28
Min Output PID Probe 3
(Oil tank exit)
Minimum value tank resistor set-point
(delta of 100°C above p29)
0,0
1000,0
80,0
°C
rE3 =1
3
70
p29
Max Output PID Probe 3
(Oil tank exit)
Maximum valuetank resistor set-point
0,0
1000,0
180,0
°C
rE3 =1
3
71
SP0
Set-point Tank Resistor with oil
pump stops (stand by)
Set-point of maintaining resistance during
stand by “
Set point adjustment
”
-50,0
200,0
140,0
°C
rE3 =1
0
72
Pb4
Probe 4
0
tcn
Setpoint Probe 4
(Oil consent)
Oil consent according table “
Set point
adjustment
”
-50,0
200,0
110,0
°C
0
73
AL4
Low Threshold Probe 4
-50,0
200,0
-50,0
°C
2
74
trS
Probe 4 - High Temperature Alarm
Threshold
(Safety Thermostat)
Tank resistor safety temperature according
table “
Set point adjustment
”
-50,0
200,0
190,0
°C
0
75
d04
Probe 4 differential
0,0
20,0
3,0
°C
2
76
Summary of Contents for TN90
Page 2: ......
Page 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 34: ...CIB UNIGAS M039259CA 34...
Page 54: ......
Page 63: ......
Page 64: ......
Page 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 82: ...M12927CA MOUNTING 2...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......