• CFG
• InFo Display
upd
(.xd
err
INF
Software
version
Self diagnostic
error code
Configuration
hrd
+8 error OUT2 card recognition
+16 error OUT3 card recognition
Information
display
0 No Error
1 Lo
2 Hi
3 ERR
4 SBR
OUTPUT 2
0 = None
1 = Relay
OUTPUT 3
0 = None
1 = Relay
SERIAL COMMUNICATION
0 = None
110
h.pb
h.it
h.dt
h.p.x
h.p.l
rst
P.rs
A.rs
ffd
sof
lb.t
lb.p
fa.p
g.sp
Proportional band for
heating or hysteresis in
regulation ON/OFF
Integral time for heating
Derivative time for
heating
Maximum power limit for
heating
Manual reset
Waiting time for LBA alarm intervention
(Set to “0” to disable LBA alarm)
Power limit for LBA
alarm condition
Power output in fault condition
(when probe is faulty)
-999 ... 999
punti scala
0 ... 999.9% f.s.
0.00 ... 99.99 min
0.00 ... 99.99 min
0.0 ... 100.0%
Minimum power limit
for heating
(not available for double heat/
cool action)
0.0 ... 100.0%
0.0 ... 500.0 min
-100.0 ... 100.0%
-100.0 ... 100.0%
ON / OFF
Set gradient
(see applicable note)
0.0...999.9 digit/min.
(digit / sec see SP.r)
Antireset
Feedforward
0 ... 9999
scale points
-100.0 ... 100.0%
Reset power
-100.0 ... 100.0%
Softstart time
0.0 ... 500.0 min
(*)
(*)
(*)
LBA alarm may be reset by simultaneously pressing
Δ
+
∇
keys when OutP is
displayed or by switching to Manual.
S.tv
CFG
Control parameters
(*) +16 with passage automatic rifle in GO if PV-SP > 0,5%
+32 with passage automatic rifle in GO if PV-SP > 1%
+64 with passage automatic rifle in GO if PV-SP > 2%
+128 with passage automatic rifle in GO if PV-SP > 4%
Enabling
self-tuning,
autotuning,
softstart
S.tun Continuous Sel-ftuning Softstart
autotuning
0
NO NO NO
1 YES
NO
NO
2 NO
YES
NO
3
YES YES NO
4
NO NO YES
5 YES
NO
YES
6
- - -
7
- - -
S.tun Autotuning Selftuning Softstart
one shot
8* WAIT
NO
NO
9 GO
NO
NO
10* WAIT
YES
NO
11 GO
YES
NO
12* WAIT
NO
YES
13 GO
NO
YES
g.s0
Setpoint gradient of
pre-heating
0.0 ... 999.9 digit / min.
(digit / sec seeSP.r)
Xt.0
Retention time of
pre-heating setpoint
0 … 200 min.
(sec see SP.r)
sp.0
Setpoint of pre-heating
Lo.L … Hi.L
g.s1
Set gradient at the end of
the pre-heating
0.0 ... 999.9 digit / min.
(digit / sec see SP.r)
0
1.2
5.83
1.33
100.0
0.0
0
0.0
0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0
0.0
0.0
4
80379_MHW_600V-T73_06-2012_ENG
Summary of Contents for TN90
Page 2: ......
Page 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 34: ...CIB UNIGAS M039259CA 34...
Page 54: ......
Page 63: ......
Page 64: ......
Page 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 82: ...M12927CA MOUNTING 2...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......