M12927CA
LIMITED ACCESS LEVEL
Proceed as follows to change some parameters that are not visible in standard user mode:
Press the
key for
3 seconds
Password = 20
Access to parameter:
Increase the displayed value
Decrease the displayed
value
Confirm and go to next
parameter
Param Description
Values
Default
SEnS
Input type
Pt1 = RTD Pt100
Pt10 = RTD Pt1000
0.20 = 0..20mA
4.20 = 4..20mA Pressure probe
0.10 = 0..10V
2.10 = 2..10V
crAL= Thermocouple K
Depends on the probe
SP
Set point 1
SPLL ... SPLH
See page 7
AL1
AL1 threshold
AL1L... AL1H (E.U.)
HAL1
AL1 hysteresis
1... 9999 (E.U.)
Pb
Proportional band
1... 9999 (E.U.)
ti
Integral time
0 (oFF) ... 9999 (s)
td
Derivative time
0 (oFF) ... 9999 (s)
Str.t
Servomotor stroke time
5...1000 seconds
db.S
Servomotor dead band
0...100%
SPLL Minimum set point value
-1999 ... SPHL
SPHL Maximum set point value
SPLL ... 9999
dp
Decimal point position
0... 3
SP 2
Set point 2
SPLL...SPLH
60
A.SP
Selection of the active set point
"SP" ... " nSP"
SP
To exit the parameter setting procedure press the
key (for 3 s) or wait until the timeout expiration (about 30 seconds)
6
Summary of Contents for TN90
Page 2: ......
Page 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 34: ...CIB UNIGAS M039259CA 34...
Page 54: ......
Page 63: ......
Page 64: ......
Page 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 82: ...M12927CA MOUNTING 2...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......