M12927CA
windows
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the
band
LHdi = Relative band alarm in alarm inside the
band
C
29 Ab1
Alarm 1 function
0... 15
+1 = Not active at power up
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
0
C
30 AL1L
-- For High and low alarms, it is the low limit
of the AL1 threshold;
-- For band alarm, it is low alarm threshold
-1999... AL1H (E.U.)
-199.9
C
31 AL1H
-- For High and low alarms, it is the high
limit of the AL1 threshold;
-- For band alarm, it is high alarm threshold
AL1L... 9999 (E.U.)
999.9
O
32 AL1
AL1 threshold
AL1L... AL1H (E.U.)
See
page 7
O
33 HAL1
AL1 hysteresis
1... 9999 (E.U.)
See
page 7
C
34 AL1d
AL1 delay
0 (oFF)... 9999 (s)
oFF
C
35 AL1o
Alarm 1 enabling during Stand-by mode and
out of range conditions
0 = Alarm 1 disabled during Stand by and out of
range
1 = Alarm 1 enabled in stand by mode
2 = Alarm 1 enabled in out of range condition
3 = Alarm 1 enabled in stand by mode and in
overrange
condition
1
GRUPPO AL2 - parametri allarme 2
Liv N° Param
Description
Values
Default
C
36 AL2t
Alarm 2 type
nonE = Alarm not used
LoAb = Absolute low alarm
HiAb = Absolute high alarm
LHAo = Windows alarm in alarm outside the
windows
LHAI = Windows alarm in alarm inside the
windows
SE.br = Sensor Break
LodE = Deviation low alarm (relative)
HidE = Deviation high alarm (relative)
LHdo = Relative band alarm in alarm out of the
band
LHdi = Relative band alarm in alarm inside the
band
SE.br
C
37 Ab2
Alarm 2 function
0... 15
+1 = Not active at power up
+2 = Latched alarm (manual reset)
+4 = Acknowledgeable alarm
+8 = Relative alarm not active at set point change
0
C
42 AL2d
AL2 hysteresis
0 (oFF)... 9999 (s)
oFF
C
43 AL2o
Alarm 2 enabling during Stand-by mode and
out of range conditions
0 = Alarm 2 disabled during Stand by and out of
range
1 = Alarm 2 enabled in stand by mode
2 = Alarm 2 enabled in out of range condition
3 = Alarm 2 enabled in stand by mode and in
overrange
condition
0
10
Summary of Contents for TN90
Page 2: ......
Page 21: ...CIB UNIGAS M039259CA 21 Fig 9 Hydraulic diagram 3ID0014 Two or more burners configuration...
Page 34: ...CIB UNIGAS M039259CA 34...
Page 54: ......
Page 63: ......
Page 64: ......
Page 65: ...RWF50 2x RWF50 3x User manual M12922CB Rel 1 0 07 2012...
Page 80: ...16 Note Specifications and data subject to change Errors and omissions excepted...
Page 81: ...KM3 Modulator USER MANUAL M12927CA Rel 1 0 10 2020...
Page 82: ...M12927CA MOUNTING 2...
Page 106: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......