UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13
3-5
3: Installation
Figure 3.2 summarises the UPS input/output cabling requirements and provides information regarding the
external fuse rating and cable sizing.
Figure 3.3 and Figure 3.4 show the connection details for single and three phase input supply models
respectively, configured for both ‘single input feed’ and ‘dual input feed’. As mentioned above, the UPS is
configured for ‘single input feed’ as standard and if a ‘dual input feed’ configuration is required the
commissioning engineer will remove the links between the input supply and bypass supply terminals and
carry out other configuration changes before turning on the equipment.
3.3.1 External supply fuse and cable rating
Figure 3.2 PowerWave 3000T External supply cable & fuse rating
Key Point:
This information is given for guidance only. All fuses, isolators and power cables must
be rated and installed in accordance with the prescribed IEC standards or local regulation – e.g.
BS7671:2008.
Rectifier
Inverter
Static Switch
FA1
Fuse B
Load
DUAL INPUT FEED
Cable D
Cable B
Fuse C
Cable C
Rectifier
Inverter
Static Switch
Fuse A
Load
SINGLE INPUT FEED (standard)
Mains (3x380/220V,
3x400/230V,
3x415/240V)
Cable D
Cable A
EXTERNAL
BATTERY
CABINET
(option)
FA2
FA1
FA2
EXTERNAL
BATTERY
CABINET
(option)
F1
F1
Int. Batts.
Int. Batts.
FA4
FA4
Output
Switch
Maint.
Bypass
IA2
IA1
Maint.
Bypass
IA2
IA1
Output
Switch
1.
Fuse
and Cable recommendations to IEC 60950-1:2001
2.
The fuse and cable rating details in the above tables are a recommendation only.
3.
The UPS must be installed to prescribed IEC or local regulations (e.g. BS7671:2008).
4.
External DC Cables and Battery fuses are bespoke to the installation.
Power (kVA)
SINGLE INPUT FEED
DUAL INPUT FEED
Fuse A
Cable A
Cable D
Fuse B
Cable B
Fuse C
Cable C
Cable D
Single phase input
7.5
1 x 40
3 x 6.0
3 x 6.0
1 x 40
3 x 6.0
1 x 40
3 x 6.0
3 x 6.0
10
1 x 63
3 x 10
3 x 10
1 x 63
3 x 10
1 x 63
3 x 10
3 x 10
12
1 x 63
3 x 10
3 x 10
1 x 63
3 x 10
1 x 80
3 x 16
3 x 16
3 Phase input
7.5
3 x 40
5 x 6.0
3 x 6.0
3 x 25
5 x 2.5
1 x 40
3 x 6.0
3 x 6.0
10
3 x 63
5 x 10
3 x 10
3 x 25
5 x 2.5
1 x 63
3 x 10
3 x 10
15
3 x 80
5 x 16
3 x 16
3 x 40
5 x 6.0
1 x 80
3 x 16
3 x 16
20
3 x 100
5 x 25
3 x 25
3 x 40
5 x 6.0
1 x 100
3 x 25
3 x 25
Summary of Contents for PowerWave 3000T
Page 1: ...Pioneering solutions for total power protection PowerWave PW 3000 T User Manual ...
Page 2: ......
Page 8: ...1 Safety 1 2 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 30: ...3 Installation 3 18 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 44: ...4 Operation 4 14 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 56: ...7 Options 7 8 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...