4: Operation
4-12
UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13
Transferring to the UPS bypass (Eco mode) from the Maintenance Bypass:
5.
Ensure that the
BYPASS
LED is green.
6.
Open the Maintenance Bypass switch (IA1).
a)
The LCD panels will display
MANUAL BYPASS OPEN
.
b)
The
INVERTER
LED will be extinguished.
c)
An audible alarm will sound.
7.
Press the
RESET
button to cancel the audible alarm.
a)
The LCD display(s) will now indicate
LOAD NOT PROTECTED
.
Transferring the load to the inverter:
8.
On the Control Panel:
a)
Press the
UP
key once to access the menu system.
b)
Use the
UP/DOWN
keys to move the cursor so that it is adjacent to
COMMANDS
and then press the
ENTER
key.
c)
Use the
UP/DOWN
keys move the cursor so that it is adjacent to
LOAD TO INVERTER
and then press
the
ENTER
key.
9.
The UPS will transfer the load to Inverter (‘On-line’ mode).
a)
The LCD display will now indicate
LOAD PROTECTED
.
b)
Check and confirm that the LED display is as shown below:
10. The UPS is now operating in ‘On-Line’ mode. The load is protected and supplied by inverter power.
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LED
Colour
LINE 1
Green
LINE 2
Green
BY PASS
Green
INVERTER
Off
BATTERY
Green
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LED
Colour
LINE 1
Green
LINE 2
Green
BY PASS
Off
INVERTER
Green
BATTERY
Green
Summary of Contents for PowerWave 3000T
Page 1: ...Pioneering solutions for total power protection PowerWave PW 3000 T User Manual ...
Page 2: ......
Page 8: ...1 Safety 1 2 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 30: ...3 Installation 3 18 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 44: ...4 Operation 4 14 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 56: ...7 Options 7 8 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...