UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13
7-1
7
Options
7.1
Introduction
The PowerWave 3000T UPS has the following available options:
• Remote Emergency Stop facilities
• Generator On facilities
• Software for automatic shutdown and monitoring
• SNMP Card for network management and remote monitoring
• Modem/Ethernet interface for PowerREPORTER™ management software
7.2
Remote Emergency Stop facilities
The remote emergency stop facility comprises a normally-closed contact connected between terminal port
X1/20 and X1/21 on the communications board which opens to operate the emergency stop function.
To allow removal, maintenance or testing of any remote emergency stop facility without disturbing the normal
operation of the UPS, it is recommended that a terminal block, with linking facilities, is installed between the
UPS and the remote emergency stop button.
1.
Use a screened cable with 1 pair of wires (0.6mm
2
) and maximum length of 100 m.
2.
Connect the cable as shown in Figure 7.1.
Figure 7.1 Remote Emergency Stop cabling
X1
X1/20
X1/21
Remote shutdown
Terminal block
UPS Remote
Shutdown Port
Cabinet B/C
Cabinet A
Summary of Contents for PowerWave 3000T
Page 1: ...Pioneering solutions for total power protection PowerWave PW 3000 T User Manual ...
Page 2: ......
Page 8: ...1 Safety 1 2 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 30: ...3 Installation 3 18 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 44: ...4 Operation 4 14 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...
Page 56: ...7 Options 7 8 UPS469 01 00 PowerWAVE 3000T User Manual Dated 05 04 13 ...