7: Options
7-2
UPS469-01-00 PowerWAVE 3000T User Manual Dated 05-04-13
7.3
Generator ON facilities
The ON GENERATOR facility uses a normally-open contact which closes when a standby generator is
running and supplying the UPS input power.
When used, this facility inhibits the operation of the battery charger and/or static bypass while the generator
is on-line. See “Set-up User menu screen” in section 4.3.7.
1.
Use a screened cable with 1 pair of wires (0.6mm
2
) and maximum length of 100 m.
2.
Connect the cable as shown in Figure 7.2.
Figure 7.2 Generator ON Connection
X1
X1/16
X1/17
ON GENERATOR
N/O contact
UPS ON GENERATOR
Port
Cabinet B/C
Cabinet A