4: Operation
4-16
UPS470-01-00 PowerWAVE 5000TP User Manual Dated 31-10-2011
Module shut-down:
Use this procedure to power down a single module in a redundant module system.
1.
Simultaneously press the two
ON/OFF
buttons on the UPS control panel.
a)
The LED display will give the following indications:
2.
Open the Parallel Isolator switch IA2.
3.
In the UPS Cabinet, open the Input supply and Bypass supply fused isolators FA1 and FA2.
4.
Open the battery fuse/isolator.
a)
Open FA3/F1 if using internal batteries.
b)
If using external batteries open the battery fuses/isolator on the associated battery cabinet/rack.
5.
Open the UPS input supply isolator and UPS output isolator on the LV Switchboard.
6.
The UPS module is now totally shut-down.
LINE 1
LINE 2
BY PASS
INVERTER
BATTERY
LOAD
LED
Colour
LINE 1
Green
LINE 2
Off
BY PASS
Off
INVERTER
Off
BATTERY
Green