6: Troubleshooting
6-2
UPS338-01-00 PowerWAVE 8000-RI DPA User Manual Dated 5 April 2013
6.3
Fault Identification and Rectification Messages and Alarms
6.4
Contacting Service
Uninterruptible Power Supplies Limited has a service department dedicated to providing routine maintenance
and emergency service cover for your UPS.
If you have any queries regarding your UPS please contact us.
We recommend that your UPS is protected by an Extended Warranty Agreement (see Section 2 for details).
These agreements assist us in caring for your UPS correctly, ensuring that it is well maintained and attended
to promptly should any problems occur.
Alarm Condition
Meaning
Suggested Solution
UPS FAULT
There is a fault in the UPS and
therefore normal operation cannot be
guaranteed
Call the authorised service centre for
assistance
MAINS BYP/RECT FAULT
Mains power supply is outside
prescribed tolerance
The input power to UPS is high/low or missing.
If site power appears to be OK, check the input
circuit breakers etc. supplying the UPS
OUTPUT SHORT
There is a short circuit at the output of
UPS (on load side)
Check all output connections and repair as
required.
OVERLOAD
Load exceeds the UPS rated power
Identify which piece of equipment is causing
the overload and remove it from the UPS.
Do not connect laser printers, photocopiers,
electric heaters, kettles etc. to the UPS
OVERTEMPERATURE
UPS temperature has exceeded the
allowed value
Check the ambient temperature of the UPS is
less than 30° C.
If the ambient temperature is normal call the
authorised service centre for assistance.
BATTERY CHARGER OFF
The attached battery and the battery
charger set-up do not correspond or
battery charger fault
Call the authorised service centre for
assistance.
INVERTER FAULT
Inverter is faulty.
Call the authorised service centre for
assistance.
SYNCHRON FAULT
The inverter and mains are not
synchronised.
The frequency of the input voltage to the UPS is
outside operational limits and the UPS static
bypass has been temporarily disabled.
BATTERY IN DISCHARGE
Battery is near end of autonomy
Shutdown load connected to UPS before the
UPS switches itself off to protect its batteries
MANUAL BYP IS CLOSED
Maintenance Bypass closed. Load
supplied by mains
This alarm is only displayed if the UPS is on
Maintenance Bypass
Uninterruptible Power Supplies Ltd.
Woodgate
Bartley Wood Business Park
Hook
Hampshire
RG27 9XA
Tel:
01256 386700
0800 731 3269 (24 Hr.)
Fax:
01256 386701
Email
:
service@upspower.co.uk
Summary of Contents for PowerWAVE 8000DPA RI
Page 1: ...User Manual PowerWAVE 8000DPA RI Pioneering solutions for total power protection ...
Page 2: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 4: ...UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 8: ... iv UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 10: ...1 Safety 1 2 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 16: ...2 General Description 2 6 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...
Page 42: ...3 Installation 3 26 UPS338 01 00 PowerWAVE 8000 RI DPA User Manual Dated 5 April 2013 ...